Installation

2.7.3 ANN-80 Remote LCD Annunciator
The ANN-80 LCD Annunciator is a compact, 80 character, backlit LCD remote fire annunciator
which mimics the FACP display. It also provides system status indicators for AC Power, Alarm,
Trouble, Supervisory and Alarm Silenced conditions. Communication between the ANN-80 and
FACP is accomplished over a two wire serial interface employing the ANN-BUS communication
format. The devices are powered, via two additional wires, from either the host FACP or remote
UL-listed, filtered, power supply.

2.7.4 Specifications

Operating Voltage Range: 18 VDC to 28 VDC
Current Consumption @ 24 VDC nominal (filtered and nonresettable):
For use indoors in a dry location
2.7.5 Installation
Ensure that all power (AC and DC) has been removed from the FACP before installing the
annunciator.

2.7.5.1 Mounting

The ANN-80 can be surface or semi-flush mounted to a single, double or 4" square electrical
box. Select and remove the appropriate knockout(s), pull the necessary wires through the
knockouts and mount the annunciator in or on the wall depending on the type of installation
desired.
The ANN-80 cover must be attached to the annunciator backplate before mounting the
annunciator to the electrical box/wall. The cover cannot be reattached or removed after the
annunciator has been mounted.

2.7.5.2 Opening/Closing Annunciator

The following procedure details the steps used to open the annunciator in order to access the
terminal block and DIP switches (refer to figure below):
1. Turn the key switch to the ON (Unlocked) position by turning the key counter-clockwise
2. Push in the snap latch located on the right side of the unit while pulling the cover open
3. To close the cover, make certain the key switch is in the ON (Unlocked) position. Swing the
cover closed, snapping it shut
4. Turn the key switch to the OFF (Locked) position by turning clockwise and remove the key
34
Normal/Standby (no activity): 37.0 mA
Trouble: 39.0 mA
Alarm: 40.0 mA
AC Fail (not backlit): 15.0 mA
Annunciator cover
with LCD display
Key switch shown
in ON position
ANN-BUS Devices
Annunciator backplate
Press in latch
and
Pull annunciator
cover open
MRP-2002 & MRP-2002E PN 53049:A1 5/01/2008