FACP Configuration Templates
Device Installation Example for Template 2
Output Circuit #2
Release Stage NAC
Output
Circuit #1
Release
Solenoid 1
Notes:
1. All End-of-Line Resistors, illustrated in this example, are 4.7KΩ, ½ watt (PN: 71252).
2. All devices are connected as Class B circuits. For details on connecting as Class A circuits,
refer to "CAC-5X Class A Converter Module" on page 26.
114
Input Circuit #1
2-Wire Smoke
Input Circuit #2
2-Wire Smoke
Input Circuit #3
Manual Release
Input Circuit #4
Abort Switch
Input Circuit #5
Pull Station
Template 2: Single Zone System With Horn
Output
Output
Circuit #3
Circuit #4
Alarm
Alarm
NAC
NAC
Input Circuit
#6
Supervisory
MRP-2002 & MRP-2002E PN 53049:A1 5/01/2008