Master Programming Level
PROGRAMMING
Pressing 3 for System Setup, while viewing Programming Screen #2, will cause the following
1=CROSS INPUT ZONES
screens to be displayed:
2=ON-BOARD RELAYS
3=SYSTEM SETUP
Programming Screen #2
MRP-2002 & MRP-2002E PN 53049:A1 5/01/2008
Charger Disable: This option allows the programmer to disable the onboard battery charger
in the event an external battery charger is being used.

1=ABORT TYPE

2=TIMERS
3=BANNER
1=TIME-DATE
2=TROUBLE REMIND
3=CHARGR DISABLE
1=CANADIAN OPTION
3.5.6.1 Abort Type
The Abort function provides the ability to stop an agent release that was initiated by an
automatic detection device. The Abort Type provides the programmer with four abort methods:
UL (UL 864 approved) - A releasing event starts the Pre-discharge timer. If the Abort
Switch is pressed while the Delay Timer continues to count down, the timer counts down
to 10 seconds and holds there. If the Abort Switch is released, the timer resumes the
countdown from 10 seconds.
IRI (UL 864 approved)- This Abort Type functions the same way as the UL type, except
that the Abort Switch will not function unless it is pressed before the cross-zoned second
input device activates
NYC - A releasing event starts the Pre-discharge timer. Pressing an Abort switch will stop
the Pre-discharge timer. Releasing the Abort switch resets the Pre-discharge timer to the
original time plus 90 seconds. The Abort switch can be operated multiple times, with each
operation resetting the Pre-discharge timer to the original time plus 90 seconds.
Local Jurisdiction - A releasing event starts the Pre-discharge timer. Pressing an Abort
switch will stop the Pre-discharge timer. Releasing the Abort switch resets the Pre-
discharge timer to the original time. The Abort switch can be operated multiple times,
with each operation resetting the Pre-discharge timer to the original time.
Note: The Abort functions will not operate if the Pre-discharge Delay timer is set to zero. Also,
activation of a Manual Release Switch will override Pre-discharge Delay and override an
active Abort Release Switch, resulting in an immediate agent release.
SYSTEM SETUP
System Setup Screen #1
SYSTEM SETUP
System Setup Screen #2
SYSTEM SETUP
System Setup Screen #3
Programming
NO
NO
OFF
65