Output Circuits

2.4 Output Circuits

2.4.1 Outputs/Notification Appliance/Releasing Circuits

Each of the four Style Y (Class B) Notification Appliance Circuits can output a maximum of 3.0
amps of current. Total current drawn from these as well as other DC power outputs cannot exceed
7.0 amps (refer to battery calculations section). Each circuit is supervised, power-limited and
provides special application power. Refer to the Device Compatibility Document for a listing of
compatible notification appliances.
The NACs can be converted to Style Z (Class A) by installing two optional Class A Converter
module. Refer to "CAC-5X Class A Converter Module" on page 26.
Class B Notification Appliance Circuits (supervised and power-limited)
Polarized Bell
Polarized Strobe
Polarized Horn
+ - +
MRP-2002 & MRP-2002E PN 53049:A1 5/01/2008
Ω
4.7 K
, ½ watt resistor P/N:71252
Releasing Solenoid
Notification Appliance Circuits
polarity shown in alarm condition
-
Figure 2.7 NAC/Output Connections
Polarized Bell
Polarized Strobe
Polarized Horn
Dummy load any unused
circuits (P/N: 71245)
+ - +
Installation
-
23