Programming
SYSTEM SETUP
1=ABORT TYPE

2=TIMERS

3=BANNER
System Setup Screen #1
66
3.5.6.2 Timers
Timers for Pre-discharge, Discharge, Waterflow Delay and AC Loss Delay can be programmed
by pressing 2 while viewing System Setup Screen #1. The following screen will be displayed:

1=PRE-DISCHARGE

2=DISCHARGE
3=WATERFLOW DELAY
1=AC LOSS DELAY
3.5.6.2.1 Pre-Discharge
The factory default setting for Pre-discharge is 0 for no delay. To select a Pre-discharge delay
of 01 to 60 seconds, press 1 for Pre-Discharge while viewing Timer Screen #1. The following
display will appear:
PRE-DISCHARGE DELAY
RANGE 00-60 SECONDS
This screen allows the user to program a specific delay time before the releasing circuit begins
an agent release during an alarm condition. A flashing cursor is positioned in the lower left
corner of the display. Enter a Pre-Discharge delay time consisting of two digits, such as 05 for
five seconds. Upon entering the second digit, the time delay will be stored in the control panel
memory and the display will return to the Delay Screen which will indicate the new Pre-
Discharge delay time. In this example, when the corresponding agent releasing circuit is
activated, it will delay agent release for five seconds.
Note that if a Manual Release is activated, the Discharge Delay time will be ignored and the
release will begin immediately.
TIMERS
1 MIN
Timer Screen #1
TIMERS
2 HR
Timer Screen #2
Pre-Discharge Setup Screen
MRP-2002 & MRP-2002E PN 53049:A1 5/01/2008
Master Programming Level
60S
90S