Agent release control system
Hide thumbs Also See for fire-lite alarms MRP-2002E:
Table of Contents

Advertisement

Installation
Combination Waterflow/Supervisory Zone
A combination Waterflow/Supervisory circuit allows an FACP to distinguish between an Alarm
switch (waterflow device) and a Supervisory switch (tamper) installed on the same circuit. Any
circuit can be programmed as a Combo Type zone. The following figure illustrates the wiring of
Zone 2 as a Style B (Class B) Waterflow/Supervisory circuit.
Supervisory Switch
(tamper)
In-Line-Resistor
1.2 KΩ, ½ watt resistor P/N: 75579
Alarm Switch
(waterflow)
Requirements for the Combination Waterflow/Supervisory circuit are as follows:
22
Class B Initiating Device Circuits (supervised and power-limited)
Ω
4.7 K
, ½ watt resistor P/N:71252
Figure 2.6 Style B Combination Circuit on Zone 2
The Waterflow Alarm Switch must connect to the FACP Initiating Device Circuit before
the In-Line Resistor as shown in Figure 2.6
The Supervisory Switch must connect to the FACP Initiating Device Circuit after the In-
Line Resistor as shown in Figure 2.6
Program the FACP Initiating Device Circuit as a Combination circuit as described in
"Input Zones" on page 50. Note that since a Waterflow Supervisory Switch is included in
a Combination circuit, the waterflow delay must be taken into consideration. Refer to
"Waterflow Delay" on page 68
Waterflow Alarm Switch activation causes the panel to latch into alarm until the alarm
condition is cleared and the FACP is reset
Supervisory Switch activation causes the panel to latch the supervisory condition if the
Combo type code is selected or track (the panel will clear when the supervisory condition
is cleared) if the Combo Autoresettable Supervisory type code is selected
Dummy load all unused
circuits - 4.7 K
resistor (P/N: 71245)
MRP-2002 & MRP-2002E PN 53049:A1 5/01/2008
Input Circuits
Ω
, ½ watt