Nfpa 72 Auxiliary Fire Alarm System - Honeywell fire-lite alarms MRP-2002E Manual

Agent release control system
Hide thumbs Also See for fire-lite alarms MRP-2002E:
Table of Contents

Advertisement

NFPA Standard-Specific Requirements
C.1 NFPA 72 Auxiliary Fire Alarm System
All connections are power-limited and supervised. This application is not suitable for separate
transmission of sprinkler supervisory or trouble conditions.
Notes:
1. 3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.
2. Cut JP30 on the MRP-2002/E main circuit board to supervise placement of 4XTMF module
and circuit.
3. Cut JP24 on the MRP-2002/E main circuit board to enable FACP Supervisory relay.
4. Refer to "4XTMF Municipal Box Transmitter Option Module" on page 28 for detailed
information.
Figure C.2 Municipal Box Connected to 4XTMF Transmitter Module
Polarities shown in alarm condition
118
Figure A.2 Municipal Box Connected to 4XTMF Transmitter Module

NFPA 72 Auxiliary Fire Alarm System

Municipal Box
Circuit
Gamewell Model M34-56
Local Energy Municipal Box
Nonpower-limited
-
+
4XTMF
MRP-2002 & MRP-2002E PN 53049:A1 5/01/2008