3.4
Faults, faults and remedy
Error
WC does not flush
WC flush runs through
Flush plate Visign for Public 6
▶
Remove the cable of the programming contact.
▶
Place a protective cap onto the contact.
Cause
Power supply failure
Cistern is not yet completely full
No water in cistern, corner valve is
closed
Control defect
Plug connection power pack /
control not made
Plug connection drive unit / control
not made
Detection area is not set correctly
Dirty seal in filling valve
Dirty seal in drain valve
Plug sequence drive unit / control
incorrect
Remedy
Check power supply
Wait until the cistern is sufficiently
full
Open corner valve
Replace control
Create plug connection
Ä 'Con‐
necting the control' on page 27
Create plug connection
Ä 'Con‐
necting the control' on page 27
Set detection area
Ä Chapter
3.3.1 'Setting the infrared sensor'
on page 34
Check seal, replace if necessary
Check seal, replace if necessary
Check plug connection, observe
coloured marking
Ä 'Connecting
the control' on page 27
Handling
43