3.4

Faults, faults and remedy

Error
WC does not flush
WC flush runs through
manual actuation is not working
3.5

Care and maintenance

3.5.1

Care tips

Flush plate Visign for Public 5
Cause
Power supply failure
Cistern is not yet completely full
No water in cistern, corner valve is
closed
Control defect
Plug connection power pack /
control not made
Plug connection drive unit / control
not made
Detection area is not set correctly
Dirty seal in filling valve
Dirty seal in drain valve
Plug sequence drive unit / control
incorrect
The mechanism is not connected
to the bow
Normal soap or a mild cleaning agent can be used for regular care and
prevention of lime scale on the flush plate. Under no circumstances
should scouring agent or scratching objects be used.
Strong stains can be removed using typical household cleaner. Rinse
the detergent thoroughly with clear water after the prescribed exposure
time. There should be no residue on the components.
Remedy
Actuate manual flush
Wait until the cistern is sufficiently
full
Open corner valve
Replace control
Create plug connection
Ä 'Con‐
necting the control' on page 27
Create plug connection
Ä 'Con‐
necting the control' on page 27
Set detection area
Ä Chapter
3.3.1 'Setting the infrared sensor'
on page 35
Check seal, replace if necessary
Check seal, replace if necessary
Check plug connection, observe
coloured marking
Ä 'Connecting
the control' on page 27
Hang the mechanism in the bow