Diagnostics - ABB Endura ACA592-TC Operating Instructions Manual

Toroidal conductivity transmitter
Table of Contents

Advertisement

Endura ACA592
Toroidal conductivity transmitter

7.3.6 Diagnostics

Menu
Diagnostics
123
Exit
Diagnostics Level
Parameter
Loop Test
Diagnosis Status
60
Used to perform a loop test (output verification) and indicate
6
the diagnostic status (actual / simulated).
Select
Description
The current output of the transmitter can be adjusted between 3.8 and 21.5 mA.
This feature is useful to verify that the transmitter output matches the current in the control
room.
Enabled when HART Poll Addr = 0 – see page 61.
Used to determine if diagnostics simulation is active (read-only).
The display should read 'Actual' indicating real-time diagnostics from the transmitter.
7 Operator Pages and Menus
OI/ACA592/TC–EN Rev. B