Benchmark 2500DF-3000DF Installation, Operation & Maintenance Manual
Igniter-Injector Maintenance Procedures - Continued
5. Next, loosen and remove the igniter-injector from the burner plate using a 1" open-end
wrench.
6. Check the igniter-injector for evidence of erosion or carbon build-up. If there is evidence
of substantial erosion or carbon build-up, the igniter-injector should be replaced. If
carbon build-up is present, clean the component using fine emery cloth. Repeated
carbon build-up is an indication that the combustion settings of the unit should be
checked. Refer to Chapter 4 for combustion calibration procedures.
COMPRESSION
FITTING &
ELBOW
O2 SENSOR
& WASHER
IGNITOR-INJECTOR
ASSY WITH INDEXING
(CLOCKING) WASHERS
(0-3 as needed)
Figure 7-2. Igniter-Injector & Flame Detector Mounting Details
7. Next, loosen and remove the igniter-injector from the burner plate using a 1" open-end
wrench.
8. Check the igniter-injector for evidence of erosion or carbon build-up. If there is evidence
of substantial erosion or carbon build-up, the igniter-injector should be replaced. If
carbon build-up is present, clean the component using fine emery cloth. Repeated
carbon build-up is an indication that the combustion settings of the unit should be
checked. Refer to Chapter 4 for combustion calibration procedures.
9. Prior to reinstalling the igniter-injector, a high temperature, conductive, anti-seize com-
pound must be applied to the threads.
OMM-0099_0A
GF-145
CHAPTER 7 – MAINTENANCE
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Ph.: 800-526-0288
BLOWER PLENUM
STAGED IGNITION
SOLENOID
FLAME
OBSERVATION
PORT
BURNER PLATE
FLANGE
FLAME
DETECTOR &
GASKET
FLEX GAS
HOSE NIPPLE
Page 93 of 234