6.6 INTERLOCK TESTS

The unit is equipped with two interlock circuits called the Remote Interlock and Delayed Interlock.
Terminal connections for these circuits are located in the I/O Box (Figure 2-12) and are labeled REMOTE
INTL'K IN and DELAYED INTL'K IN. These circuits can shut down the unit in the event that an interlock
is opened. These interlocks are shipped from the factory jumpered (closed). However, each of these
interlocks may be utilized in the field as a remote stop and start, an emergency cut-off, or to prove that a
device such as a pump, gas booster, or louver is operational.

6.6.1 Remote Interlock Test

1. Remove the cover from the I/O Box and locate the REMOTE INTL'K IN terminals.
2. Start the unit in the Manual Mode and set the valve position between 25% and 30%.
3. If there is a jumper across the REMOTE INTL'K IN terminals, remove one side of the
jumper. If the interlock is being controlled by an external device, either open the interlock
via the external device or disconnect one of the wires leading to the external device.
4. The unit should shut down and display INTERLOCK OPEN.
5. Once the interlock connection is reconnected, the INTERLOCK OPEN message should
automatically clear and the unit should restart.

6.6.2 Delayed Interlock Test

1. Remove the cover from the I/O Box and locate the DELAYED INTL'K IN terminals.
2. Start the unit in the Manual Mode at a valve position between 25% and 30%.
3. If there is a jumper across the DELAYED INTL'K IN terminals, remove one side of the
jumper. If the interlock is connected to a proving switch of an external device, disconnect
one of the wires leading to the proving switch.
4. The unit should shut down and display a DELAYED INTERLOCK OPEN fault message.
The FAULT LED should be flashing.
5. Reconnect the wire or jumper removed in step 3 to restore the interlock.
6. Press the CLEAR button to reset the fault
7. The unit should start.
Page 82 of 234
05/21/2014
CHAPTER 6 – SAFETY DEVICE TESTING
Remote Interlock Test
Delayed Interlock Test