Benchmark 2500DF-3000DF Installation, Operation & Maintenance Manual
APPENDIX B – STARTUP, STATUS & DISPLAY MESSAGES
Table B-1: Startup, Status, And Display Messages - Continued
FAULT MESSAGE
LOW WATER
LEVEL
NETWORK COMM
FAULT
O
% OUT OF RANGE
2
OUTDOOR TEMP
SENSOR FAULT
OUTLET TEMP
SENSOR FAULT
PRG SWTCH CLOSED
DURING IGNITION
PRG SWTCH OPEN
DURING PURGE
REMOTE SETPT
SIGNAL FAULT
RESIDUAL
FLAME
SSOV
SWITCH OPEN
SSOV FAULT
DURING PURGE
SSOV FAULT
DURING IGN
SSOV FAULT
DURING RUN
SSOV RELAY
FAILURE
STEPPER MOTOR
FAILURE
OMM-0099_0A
GF-145
The Low Water Cutoff board is indicating low water level.
The RS-485 network information is not present or is corrupted.
The O
% has gone below 3% or above 8%.
2
The temperature measured by the Outdoor Air Sensor is out of
range.
The temperature measured by the Outlet Sensor is out of
range:
• OUTLET TEMPERATURE display = SHt Indicates sensor is
shorted
• OUTLET TEMPERATURE display = Opn indicates sensor is
open-circuited
The Purge Position Limit Switch on the Air/Fuel Valve closed
during ignition.
The Purge Position Limit Switch on the Air/Fuel Valve opened
during purge.
The Remote Setpoint signal is not present or is out of range.
The Flame signal was seen for more than 60 seconds during
standby.
The SSOV switch opened during standby.
The SSOV switch opened during purge.
The SSOV switch closed or failed to open during ignition.
The SSOV switch closed for more than 15 seconds during run.
A failure has been detected in one of the relays that control the
SSOV.
The Stepper Motor failed to move the Air/Fuel Valve to the
desired position.
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Ph.: 800-526-0288
FAULT DESCRIPTION
Page 149 of 234