3.8 COMBUSTION CAL MENU

The Combustion Cal (Calibration) Menu is protected by the level 2 password (6817) which must be
entered to view or change the menu items shown in Table 3-6. These menu items are used to vary the
speed of the unit's blower motor based on air temperature and air density at prescribed Air/Fuel Valve
positions (% open). This is accomplished by providing a DC drive voltage to the motor which adjusts the
rotational speed of the blower to maximize combustion efficiency and ensure the unit conforms to the
Nitrogen Oxide (NOx) and Carbon Monoxide (CO) emissions specified in Chapter 4. The valve positions
(%) and default drive voltages are listed in Table 3-6.
Table 3-6: Combustion Cal Menu for Natural Gas and Propane Gas
Natural Gas
Menu Item Display
CAL Voltage 14%
CAL Voltage 30%
CAL Voltage 45%
CAL Voltage 65%
CAL Voltage 85%
CAL Voltage 100%
SET Valve Position
Monitor Blower Output Voltage
Set Stdby Volt
Oxygen Level
Natural Gas
Menu Item Display
CAL Voltage 16%
CAL Voltage 20%
CAL Voltage 30%
CAL Voltage 45%
CAL Voltage 70%
CAL Voltage 100%
SET Valve Position
Monitor Blower Output Voltage
Set Stdby Volt
Oxygen Level
OMM-0099_0A
GF-145
CHAPTER 3 – OPERATION
BMK3000 Boiler Cal Menu
Default
2.40
5.40
6.60
7.00
8.00
8.7
Variable
0.0 V
Variable
BMK2500 Boiler Cal Menu
Default
2.15
2.10
3.85
5.60
6.60
8.50
Variable
0.0 V
Variable
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Ph.: 800-526-0288
Propane Gas
Menu Item Display
CAL Voltage 18%
CAL Voltage 30%
CAL Voltage 45%
CAL Voltage 65%
CAL Voltage 85%
CAL Voltage 100%
SET Valve Position
Monitor Blower Output Voltage
Set Stdby Volt
Oxygen Level
Propane Gas
Menu Item Display
CAL Voltage 18%
CAL Voltage 22%
CAL Voltage 30%
CAL Voltage 45%
CAL Voltage 70%
CAL Voltage 100%
SET Valve Position
Monitor Blower Output Voltage
Set Stdby Volt
Oxygen Level
Default
2.30
4.40
5.40
5.70
7.00
8.60
Variable
0.0 V
Variable
Default
2.00
2.00
3.30
4.60
5.60
7.90
Variable
0.0 V
Variable
Page 43 of 234
PR1: 05/21/2014