Data Log Viewing Procedure – Continued
7. Shortcut keys are also available to go directly to a specific menu. These shortcut keys are:
m0
Default (Operating) Menu
m1
Setup Menu
m2
Configuration Menu
m3
Tuning Menu
m4
Calibration Menu
m5
Diagnostic Menu
8. To change a value or setting for a displayed menu option, proceed as follows:
(a) Enter C, followed by the number to the right of the displayed option to be changed,
and then press <Rtn>.
(b) Enter the desired value or setting for the option and press <Rtn>. Refer to Chapter 3,
Tables 3-2 through 3-5 for allowable entry ranges and settings for the Operating,
Setup, Configuration and Tuning Menus. (The Calibration and Diagnostic Menus
should only be used by Factory-Trained service personnel).
(c) Menu changes will be stored in non-volatile memory.
9. To redisplay the menu and view the option which was just changed in step 5, enter D and
press <Rtn>.
10. To display the Fault (F) Log, Sensor (S) Log or Time (T) Line Log, press F, S or T
followed by <Rtn>. Refer to section 9.4 for descriptions and samples of these data logs.
11. To log off and terminate the RS232 communication link, press L followed by <Rtn>.

9.4 DATA LOGGING

During operation, the C-More Control Panel continuously monitors and logs data associated with
operational events, faults and sensor readings associated with the boiler system. Descriptions of these
data logs are provided in the following sections. The procedure for accessing specific data logs is
described in section 9.3, step 10.

9.4.1 Fault Log

The C-More Control Panel logs the last 20 faults (0 – 19) starting with the most recent (#0). They can be
viewed in the front panel display or via the RS232 port. The Fault Log cannot be cleared. If the Fault Log
already contains 10 faults, the earliest fault is overwritten when a new fault occurs. A sample Fault Log
display is shown in Table 9-1.
No.
Fault Message
0
Direct Drive Signal Fault
1
Low Gas Pressure
2
Loss of Power
The Operation Time (T) Log can store thousands of records.
Therefore, to view the most recently logged record, enter "T"
followed by 0 (zero) and press Enter (i.e. T0 <Enter>). To view
earlier records in reverse chronological order, enter T and press
Enter. To go back 200 or 1000 records, enter T200 or T1000, etc.
and press Enter.
Page 122 of 234
05/21/2014
Benchmark 2500DF-3000DF
CHAPTER 9. RS232 COMMUNICATION
Table 9-1: Sample Fault Log Display
NOTE
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Phone: 800-526-0288
Cycle
Date
Time
609
1/10/02
8:42am
366
7/04/01
5:29pm
0
1/01/01
11:50am
OMM-0099_0A
GF-145