Appendix C - Sensor Resistance/Voltage Chart - Aerco BENCHMARK 2500DF User Manual

Dual fuel gas-fired boiler
Table of Contents

Advertisement

Benchmark 2500DF-3000DF Installation, Operation & Maintenance Manual
APPENDIX C – SENSOR RESISTANCE/VOLTAGE CHART
Temperature Sensor Resistance Voltage Chart (Balco)
OMM-0099_0A
GF-145
APPENDIX C – SENSOR RESISTANCE/VOLTAGE CHART
TEMP (°F)
RES (OHMS)
-40
-30
-20
-10
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Ph.: 800-526-0288
VOLTS*
779.0
1.93
797.5
1.96
816.3
1.99
835.4
2.02
854.8
2.05
874.6
2.07
894.7
2.10
915.1
2.12
935.9
2.15
956.9
2.17
978.3
2.20
1000.0
2.23
1022.0
2.25
1044.4
2.27
1067.0
2.30
1090.0
2.32
1113.3
2.34
1137.0
2.36
1160.9
2.39
1185.2
2.41
1209.5
2.43
1234.7
2.45
1260.0
2.47
1285.6
2.50
1311.4
2.52
1337.7
2.54
1364.2
2.56
1391.0
2.58
1418.2
1445.7
Page 151 of 234
PR1: 05/21/2014

Advertisement

Table of Contents
loading

This manual is also suitable for:

Benchmark 3000df

Table of Contents