Benchmark 5000-6000 Boiler Operation-Service-Maintenance Guide CONTENTS (This page intentionally blank) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 4 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
FORWARD FOREWORD The AERCO Benchmark (BMK) 5000 MBH (1465 kW) and 6000 MBH (1758 kW) natural gas and dual fuel propane/natural gas fueled boilers are modulating and condensing units. They represent a true industry advance that meets the needs of today's energy and environmental concerns.
Page 6
BTUs per Hour (1 BTU/hr = 0.29 W) Combination Control Panel Combination Control System A control system developed by AERCO and currently used in all C-More Controller Benchmark, Innovation and KC1000 Series product lines. Cubic Feet per Hour (1 CFH = 0.028 m...
Page 7
Primary Micro-Controller (PMC) board, contained in the C-More Part Number Proof of Closure Parts per Million Pounds per Square Inch (1 PSI = 6.89 kPa) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 7 of 136 Ph.: 800-526-0288 GF-208...
Page 8
W.C. Water Column, a unit of pressure (1 W.C. = 249 Pa) µA Micro amp (1 million of an ampere) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 8 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
In addition to all the requirements included in this AERCO Instruction Manual, the installation of units MUST conform with local building codes, or, in the absence of local codes, ANSI Z223.1 (National Fuel Gas Code Publication No. NFPA-54) for gas-fired boilers and ANSI/NFPASB for LP gas-fired boilers.
Section 5: Safety Device Testing of the Benchmark 5000 – 6000 Installation and Startup Guide, OMM-0123 (GF-207) be performed to verify that all system-operating parameters are correct. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 10 of 136 OMM-0124_0B Ph.: 800-526-0288...
The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS". (Continued) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 11 of 136 Ph.: 800-526-0288...
Page 12
……………….[End of Extracted Information From 248 CMR 5.08 (2)]………………… AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 12 of 136 OMM-0124_0B Ph.: 800-526-0288...
All of the installation procedures in Section 2 of the Benchmark 5000 – 6000 Installation and Startup Guide, OMM-0123 (GF-207) must have been completed before attempting to start the unit. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 13 of 136 Ph.: 800-526-0288...
Table 2-1. Additional information on these items is provided in the individual operating procedures and menu descriptions provided in this section. Figure 2-1: C-More Controller Front View AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 14 of 136 OMM-0124_0B Ph.: 800-526-0288...
Page 15
• Pressing RESET resets the water level monitor circuit. switches • Pressing the CLEAR key (item 6) resets the display. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 15 of 136 Ph.: 800-526-0288 GF-208 12/01/2017...
Page 16
20 segment red LED bargraph continuously shows the Air/Fuel VALVE POSITION Valve position in 5% increments from 0 to 100% Bargraph AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 16 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017...
The menu option choices do not wrap around. 7. To select and store a changed menu item, press the ENTER key. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 17 of 136 Ph.: 800-526-0288...
Page 18
Refer to Appendix A in this guide for detailed descriptions of each menu option. Refer to Appendix B for listings and descriptions of displayed startup, status and error messages. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 18 of 136 OMM-0124_0B Ph.: 800-526-0288...
* NOTE Manual Valve Pos does not appear in this menu unless you push the Auto/Man button on the C-More Controller’s front face. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 19 of 136 Ph.: 800-526-0288...
E, G, H, R, N or A Unit Year Unit Serial # 9999 Current software Software Ver 0.00 Ver 9.99 version AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 20 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
100°F 60°F (If Outdoor Sensor = (-1.1° (37.8° (15.6° Enabled) Setpt Lo Limit 40°F (4.4° 60°F (15.6° Setpt Hi Limit AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 21 of 136 Ph.: 800-526-0288 GF-208 12/01/2017...
Page 22
Sensor menu item is set to Enabled. CAUTION! DO NOT change the Analog Output menu item from its default setting (Valve Position 0- 10V). AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 22 of 136 OMM-0124_0B Ph.: 800-526-0288...
Monitor Blower Output Voltage Set Stdby Volt 4.00 V 0/2.00 V 4.00 V 0/2.00 V 10 Oxygen Level Variable Variable AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 23 of 136 Ph.: 800-526-0288 GF-208 12/01/2017...
Head Temp Source Network FFWD Temp FFWD Temp Mdbus Temp Units Degrees C or Degrees F Degrees C Header Temp Addr AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 24 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
Page 25
1°F (-17.2°C) 120°F (48.9°C) 100°F (37.8°C) BST Intgral Gain 0.00 2.00 0.50 BST Deriv Time 0.00 Min 2.00 Min 0.10 Min AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 25 of 136 Ph.: 800-526-0288 GF-208 12/01/2017...
Page 26
Unit 2 is Off Unit 4 is Not Available Unit 5 is Lead On Unit 6 is Lag Off 1 BST Units 8 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 26 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017...
-5.0% 5.0% 0.0% Gas Plate dp In Adj -5.0% 5.0% 0.0% mA Out Adj -1.0 mA 1.0 mA 0.0 mA AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 27 of 136 Ph.: 800-526-0288 GF-208 12/01/2017...
Page 28
Depends on unit type/size Min Spark Amps 0 Amps 2.5 Amps 0.1 Amps Max Spark Amps 0 Amps 2.5 Amps 0.4 Amps AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 28 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
I/O Box. Refer to Section 2.10: AC Electrical Power Wiring of the Benchmark 5000 – 6000 Installation and Startup Guide, OMM-0123 (GF-207) for additional information on wiring.. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 29 of 136 Ph.: 800-526-0288...
AERCO representative be contacted. For descriptions of temperature-related functions, see Appendix A; their factory defaults are included in Sections 2.4 – 2.8. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 30 of 136 OMM-0124_0B Ph.: 800-526-0288...
Remote Setpoint Remote Signal 4-20mA/1-5V, 0-20mA/0-5V, or Network Refer to Section 2.3 for detailed instructions on changing C-More Controller menu options. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 31 of 136 Ph.: 800-526-0288 GF-208...
While it is possible to change the settings of temperature related functions, the unit is factory preset with settings that work well in most applications. It is suggested that an AERCO representative be contacted, prior to changing any temperature related function settings. For descriptions of temperature-related functions, see Appendix A;...
REMOTE LED will again light and the MANUAL LED will go off. This will happen automatically after 1 hour after the password has expired. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 33 of 136 Ph.: 800-526-0288...
Benchmark 5000 – 6000 Installation and Startup Guide, OMM-0123 (GF-207)). The ACS mode of operation is used in conjunction with an AERCO Control System. The ACS mode is used when it is desired to operate multiple units in the most efficient manner possible.
Only the AERCO Control System (ACS) is necessary to configure this system if only a single valve is used to switch from space heating to domestic hot water. However, the ACS Relay...
These default settings work well in most applications. It is suggested that AERCO be contacted prior to changing settings other than the unit’s setpoint. For descriptions of temperature-related functions, see Appendix A; their factory defaults are included in Sections 2.4 –...
Replace 15 mins. * Only performed after initial 6 month period after initial startup. The following maintenance kits are available through your local AERCO Sales Representative: NOTE: The 24-Month Waterside/Fireside Inspection Kits includes the items contained in the Annual Maintenance Kit (P/N 58025-11). Therefore, when performing the waterside/fireside inspections, only the 24-Month kit is required.
Pilot Burner from the unit after it has cooled to room temperature. PILOT BURNER PILOT BURNER ROD ROD TIP (P/N 66100) Figure 4-1b: Pilot Burner & Pilot Ignition Rod – Cross-Section AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 38 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
Page 39
12. Reconnect the ignition cable. 13. Close the right side door and front panel. Replace the top panel if the unit was serviced from above. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 39 of 136 Ph.: 800-526-0288...
Sensor Cover and holding it in place with a length of cord or wire. 3. Disconnect the O sensor lead wire by pushing in on the release tab and pulling apart the connector. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 40 of 136 OMM-0124_0B Ph.: 800-526-0288...
Page 41
GAS LINE TO EXHAUST AIR EDUCTOR MANIFOLD ASSY. For AERtrim (P/N 24508-TAB) Figure 4-2: O Sensor Mounting Location – Back Panel Semi-Transparent AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 41 of 136 Ph.: 800-526-0288 GF-208 12/01/2017...
Page 42
AIR FILTER COVER BRACKET (Hangs on opening in back panel) Figure 4-3: Air Eductor Assembly – Shown Removed from Unit AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 42 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
NOT be lit when in AUTO mode. 12. If the Pilot Regulator is NOT within specifications, proceed to Section 4.5.2 and perform the Pilot Regulator Pressure Calibration procedure. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 43 of 136 Ph.: 800-526-0288...
Page 44
(Install manometer here for Pilot Regulator test) PROPANE PILOT REGULATOR Figure 4-4b: BMK 5000/6000 Dual Fuel Pilot Regulator Mounting Location AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 44 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
NOTE: If you do not see the orange glow, contact AERCO technical support to ascertain the problem. If you DO see it, proceed to the next step. 10. If the manometer reading is below 4.6” W.C. (1.15 kPa), increase the regulator setting by rotating the adjustment screw clockwise (CW).
The results of the tests should be recorded in a log book. See the Benchmark 5000 – 6000 Installation and Startup Guide, OMM-0123 (GF-207)for a description and instructions for performing these tests. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 46 of 136 OMM-0124_0B Ph.: 800-526-0288...
13. Remove the two inlet air filters from the galvanized WYE-duct. 14. Disconnect the wires from the Blower Proof and Blocked Inlet switches (Figure 4-5b). 15. Disconnect the Molex connector from the temp sensor. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 47 of 136 Ph.: 800-526-0288...
Page 48
BLOWER FLANGE MAIN FLAME DETECTOR PILOT FLAME DETECTORS PILOT BLOWER BURNER Figure 4-5a: Burner Assembly Mounting Details – Right-Front View AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 48 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
7. Disconnect the wires from the thermal switch on the rear plate. 8. Remove all of the nuts from the rear plate, EXCEPT for the one at the top of the plate. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 50 of 136 OMM-0124_0B Ph.: 800-526-0288...
Page 51
A borescope can be used to inspect the front tubesheet as well as under the expansion joints. 16. Following inspection, reinstall the components in the reverse order in which they were removed. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 51 of 136 Ph.: 800-526-0288...
Page 52
Figure 4-8: Partial Rear View Showing Rear Burner Plate METAL TABS (4 EACH) REFRACTORY REFLECTOR Figure 4-9: Partial Rear View – Rear Plate and Refractory Removed AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 52 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
As previously mentioned, it is much easier to remove the rear refractory to inspect the combustion chamber of the unit. However if the front refractory must be replaced, order the AERCO Front Refractory Replacement kit, P/N 27103, which includes full instructions in Technical Instruction Document TID-0117.
7. Replace the front panel on the unit and return boiler to service use. AIR FILTER CLAMPS AIR FILTERS Figure 4-11: Air Filter Location AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 55 of 136 Ph.: 800-526-0288...
6. Open the drain valve and drain all water from the unit. 7. Refer to Appendix J for maintenance of blower during shut down. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 58 of 136 OMM-0124_0B Ph.: 800-526-0288...
The blower can be damaged if it is unused for a prolonged period of time. If this occurs, it is critical that you complete the instructions for Long Term Blower Storage in Appendix J. Failure to complete these instructions will void all warranties. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 59 of 136 Ph.: 800-526-0288...
2. Disconnect Wire 153 (dotted line) from Terminal 3 and connect it to the Low Gas Pressure Switch. WIRE 153 – FROM C-MORE LOW GAS PRESSURE SWITCH Figure 4-16: Wiring Diagram After Replacing Actuator AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 60 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
The front panel of the C-More Controller contains an RS232 port. This port is used only by factory-trained personnel to monitor onAER communications via a portable computer. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 61 of 136 Ph.: 800-526-0288...
Page 62
Benchmark 5000-6000 Boiler Operation-Service-Maintenance Guide SECTION 5 – TROUBLESHOOTING GUIDE (This page intentionally blank) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 62 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
Page 63
Air/Fuel Valve dial. Check igniter-injector for soot or erosion of electrode. Check Hard light. injector solenoid valve to insure proper open/close operation. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 63 of 136 Ph.: 800-526-0288...
Page 64
See CORRECTIVE ACTIONS from 3 to 12 for AIRFLOW FAULT Probable causes from 3 to 16 for AIRFLOW DURING IGNITION. FAULT DURING IGNITION applies for this fault. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 64 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017...
Page 65
Chapter. Check scanner Red LED. It should change from flashing to steady when pointed at a small flame from a match or lighter. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 65 of 136 Ph.: 800-526-0288...
Page 66
If exhaust temperature is greater than 200 F (93.3 C), check combustion calibration. combustion calibration. Calibrate or repair as necessary. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 66 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
Page 67
Replace the refractory at the hottest end plate. Check incoming voltage, set VFD to “Remote” mode. VFD is in “Local” mode, or voltage dropped below threshold. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 67 of 136 Ph.: 800-526-0288 GF-208...
Page 68
Defective IGST Board. Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF every second. If not, replace IGST Board. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 68 of 136 OMM-0124_0B Ph.: 800-526-0288...
Page 69
Measure NATURAL GAS pressure at the Low Gas Pressure Pressure) switch. If it is greater than 2.6” W.C. (650 Pa), measure continuity across the switch and replace if necessary. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 69 of 136 Ph.: 800-526-0288...
Page 70
Check resistance of sensor to determine if it is within specification. FAULT Incorrect Sensor. Ensure that the correct sensor is installed. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 70 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017...
Page 71
Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF every second. If not, replace IGST Board. RECIRC PUMP Internal recirculation pump failed. 1. Replace recirculation pump. FAILURE AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 71 of 136 Ph.: 800-526-0288 GF-208 12/01/2017...
Page 72
Check SSOV power wiring. Hot and Neutral reversed at SSOV. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 72 of 136 OMM-0124_0B Ph.: 800-526-0288...
Page 73
SSOV FAULT Check scanners sensed pilot flame. DURING Check power through ignition relay. IGNITION Scanners close neutral side of relay coil. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 73 of 136 Ph.: 800-526-0288 GF-208 12/01/2017...
Check to ensure that the IGST and Power Supply Boards are Rev. E Air/Fuel Valve “hunting” at C-More Controller are outdated. or higher. the 70% Valve Position AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 74 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017...
Page 75
- BMK 6000 – 8.5” W.C., 2.1 kPa - BMK 5000 – 4.5” W.C., 1.1 Figure 5-1: Gas Train Component and Pilot Gas Valve Location AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 75 of 136 Ph.: 800-526-0288...
Page 76
BRASS HEX HEAD (Remove to access the Gas Pressure Adjustment Screw). COVER SCREW Figure 5-3: SSOV Actuator With Gas Pressure Adjustment (SKP25) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 76 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
Page 77
Benchmark 5000-6000 Boiler Operation-Service-Maintenance Guide SECTION 5 – TROUBLESHOOTING GUIDE Continued on Sheet 2 Figure 5-4a: Pilot Assembly Troubleshooting Flow Chart (Sheet 1 of 2) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 77 of 136 Ph.: 800-526-0288...
Page 78
Benchmark 5000-6000 Boiler Operation-Service-Maintenance Guide SECTION 5 – TROUBLESHOOTING GUIDE Continued from Sheet 1 Figure 5-4b: Pilot Assembly Troubleshooting Flow Chart (Sheet 2 of 2) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 78 of 136 OMM-0124_0B Ph.: 800-526-0288...
Displays the elapsed time between 120VAC being applied to the SSOV Time to OPN Gas Valve and confirmation of gas valve opening (POC). AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 79 of 136 Ph.: 800-526-0288...
Page 80
Run Hours Fault Log Displays information on the last 20 faults. Manual Valve Pos Selects valve position. Available in Manual mode only! AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 80 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017...
4-digit serial # on the Code Plate, e.g., G-12- Software Version Identifies the current software version of the C-More Controller. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 81 of 136 Ph.: 800-526-0288...
°C) setting to allow the unit to run. Max Valve Position Sets the maximum allowable valve position for the unit. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 82 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017...
Page 83
Valve Position In reaches the Start Level value (Calibration menu item 37). There will not be a one minute delay when firing at the 29% Valve Position level. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 83 of 136 Ph.: 800-526-0288...
Page 84
When set to Enabled, the AERtrim menu options appears. O2 Trim Menu When set to Enabled, the BST menu options appears. BST Menu AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 84 of 136 OMM-0124_0B Ph.: 800-526-0288...
Range = 0 - 240 seconds Default = 20 seconds Reset Defaults? Allows Tuning menu options to be reset to their Factory Default values. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 85 of 136 Ph.: 800-526-0288 GF-208...
Permits the Standby Voltage to be set from 0 to 4.00 Set Stby V out Volts. Permits the combustion oxygen level to be displayed Oxygen Level (0% to 25%). AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 86 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
Allows adjustment of the analog input from -5.0% to +5.0%. Allows adjustment of the water Flow Rate Input from Flow In Adj -5.0% to +5.0%. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 87 of 136 Ph.: 800-526-0288...
Page 88
Range: -20 to + 20 (either ºF or °C) – Outdr Air Offset Range: -20 to + 20 (either ºF or °C) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 88 of 136 OMM-0124_0B Ph.: 800-526-0288...
Page 89
Min Spark Amps transformer input. Allows the adjustment of the maximum spark current required at the spark Max Spark Amps transformer input. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 89 of 136 Ph.: 800-526-0288 GF-208...
Page 90
Benchmark 5000-6000 Boiler Operation-Service-Maintenance Guide APPENDIX A: BOILER MENU DESCRIPTIONS (This page intentionally blank) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 90 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
The time and date are also displayed. WAIT Prompts the operator to wait. WARMUP Displayed for 2 minutes during the initial warm-up only. XX sec AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 91 of 136 Ph.: 800-526-0288 GF-208 12/01/2017...
INTERLOCK The Remote Interlock is open. OPEN LINE VOLTAGE The Line (Hot) and Neutral wires are reversed. OUT OF PHASE AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 92 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
Page 93
A failure has been detected in one of the relays that control the SSOV. FAILURE STEPPER MOTOR The Stepper Motor failed to move the Air/Fuel Valve to the desired position. FAILURE AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 93 of 136 Ph.: 800-526-0288 GF-208 12/01/2017...
Page 94
Benchmark 5000-6000 Boiler Operation-Service-Maintenance Guide APPENDIX B – STARTUP, STATUS, AND DISPLAY MESSAGES (This page intentionally blank) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 94 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
0123 (GF-207 Perform a slow drain test per ASME Boiler and Slow drain test Semi-Annual Operator Pressure Vessel Code, Sect. IV. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 97 of 136 Ph.: 800-526-0288 GF-208 12/01/2017...
Page 98
See Section 4.9 of this guide. Verify oxygen level is between 3% and 8% during Oxygen (O ) Level Monthly Operator boiler operation. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 98 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
10/12/2017 AERCO International, Inc. Whole Boiler P/N 28500-TAB (BMK 6000) Blauvelt, NY 10913 Sheet 1 of 7 28657-TAB (BMK 5000) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 103 of 136 Ph.: 800-526-0288 GF-208 12/01/2017...
Page 104
10/12/2017 AERCO International, Inc. Whole Boiler P/N 28500-TAB (BMK 6000) Blauvelt, NY 10913 Sheet 2 of 7 28657-TAB (BMK 5000) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 104 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
Page 105
10/12/2017 AERCO International, Inc. Whole Boiler P/N 28500-TAB (BMK 6000) Blauvelt, NY 10913 Sheet 3 of 7 28657-TAB (BMK 5000) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 105 of 136 Ph.: 800-526-0288 GF-208 12/01/2017...
Page 106
10/12/2017 AERCO International, Inc. Whole Boiler P/N 28500-TAB (BMK 6000) Blauvelt, NY 10913 Sheet 4 of 7 28657-TAB (BMK 5000) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 106 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
Page 107
10/12/2017 AERCO International, Inc. Whole Boiler P/N 28500-TAB (BMK 6000) Blauvelt, NY 10913 Sheet 5 of 7 28657-TAB (BMK 5000) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 107 of 136 Ph.: 800-526-0288 GF-208 12/01/2017...
Page 108
10/12/2017 AERCO International, Inc. Whole Boiler P/N 28500-TAB (BMK 6000) Blauvelt, NY 10913 Sheet 6 of 7 28657-TAB (BMK 5000) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 108 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
Page 109
10/12/2017 AERCO International, Inc. Whole Boiler P/N 28500-TAB (BMK 6000) Blauvelt, NY 10913 Sheet 7 of 7 28657-TAB (BMK 5000) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 109 of 136 Ph.: 800-526-0288 GF-208 12/01/2017...
Page 110
Benchmark 5000 & 6000 FM Gas Train 10/19/2017 International, Inc. 22222 rev F Blauvelt, NY 10913 Sheet 1 of 1 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 110 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
Page 111
Benchmark 5000 DF 6000 DF Gas Train AERCO 01/16/2017 International, Inc. Blauvelt, NY 10913 P/N 22187 rev D Sheet 1 of 1 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 111 of 136 Ph.: 800-526-0288 GF-208 12/01/2017...
Page 112
01/16/2017 International, Inc. Blauvelt, NY 10913 Sheet 1 of 1 22185 rev F (Component of DF Gas Train P/N 22187) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 112 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
Page 113
01/16/2017 International, Inc. Blauvelt, NY 10913 Sheet 1 of 1 P/N 22186 rev E (Component of DF Gas Train P/N 22187) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 113 of 136 Ph.: 800-526-0288 GF-208...
Page 114
AERCO International, Inc. BMK 5000: 24495-TAB rev A Blauvelt, NY 10913 Sheet 1 of 1 BMK 6000: 24328-4 rev H AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 114 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
APPENDIX G – WIRING DIAGRAMS BMK 5000/6000 STANDARD FUEL MODEL WIRING DIAGRAMS Standard BMK 5000/6000 Drawing Number: 22222 rev B Gas Train Wiring Diagram Sheet 1 of 1 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 127 of 136 Ph.: 800-526-0288...
Page 128
Benchmark 5000-6000 Boiler Operation-Service-Maintenance Guide APPENDIX G – WIRING DIAGRAMS Drawing Number: 63035-2 rev B, Duel Fuel Selector Switch AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 128 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
TABLE I-3: Optional Spare Parts DESCRIPTION PART NUMBER C-More Controller 69186‐4 Temperature Sensor, 1‐1/2" 123449 Lean Oxygen Sensor 61026 Over Temp‐Auto Reset Switch 123966 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 131 of 136 Ph.: 800-526-0288 GF-208 12/01/2017...
Page 132
Benchmark 5000-6000 Boiler Operation-Service-Maintenance Guide APPENDIX I – RECOMMENDED SPARE PARTS (This page intentionally blank) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 132 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
Rotate wheel a minimum of 10 full revolutions to keep the motor bearing grease from separating and drying out. (THIS STEP IS CRITICAL!) (Continued) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 133 of 136 Ph.: 800-526-0288 GF-208...
Page 134
8. MOTOR 9. RISER BLOCKS * 10. RISER BASE * * IF REQUIRED Figure J-1: Benchmark 6000 Blower Exploded View AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 134 of 136 OMM-0124_0B Ph.: 800-526-0288 12/01/2017 GF-208...
Page 135
Benchmark 5000-6000 Boiler Operation-Service-Maintenance Guide NOTES: AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0124_0B Page 135 of 136 Ph.: 800-526-0288 GF-208 12/01/2017...