Benchmark 2500DF-3000DF Installation, Operation & Maintenance Manual
Table A-1: Boiler Menu Item Descriptions – Continued
MENU LEVEL & OPTION
NOTE: The Level 2 Password (6817) must be entered to view the options in the Combustion Cal Menu.
This Menu is used during the Combustion Calibration procedures described in Chapter 4 of this Manual.
Natural Gas
CAL Voltage 14%
CAL Voltage 30%
CAL Voltage 45%
CAL Voltage 65%
CAL Voltage 85%
CAL Voltage 100%
Set Valve Position
Blower Output
Set Stby V out
Oxygen Level
MENU LEVEL & OPTION
NOTE: The Level 2 Password (6817) must be entered to view the options in the Combustion Cal Menu.
This Menu is used during the Combustion Calibration procedures described in Chapter 4 of this Manual.
Natural Gas
CAL Voltage 16%
CAL Voltage 20%
CAL Voltage 30%
CAL Voltage 45%
CAL Voltage 70%
CAL Voltage 100%
Set Valve Position
Blower Output
Set Stby V out
Oxygen Level
OMM-0099_0A
GF-145
APPENDIX A – BOILER MENU ITEM DESCRIPTIONS
BMK 3000
COMBUSTION CAL MENU
Propane Gas
CAL Voltage 18%
CAL Voltage 30%
CAL Voltage 45%
CAL Voltage 65%
CAL Voltage 85%
CAL Voltage 100%
BMK 2500
COMBUSTION CAL MENU
Propane Gas
CAL Voltage 18%
CAL Voltage 22%
CAL Voltage 30%
CAL Voltage 45%
CAL Voltage 70%
CAL Voltage 100%
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Ph.: 800-526-0288
DESCRIPTION
Displays the default DC drive voltage provided to
the blower at each of the Air/Fuel Valve positions
show in the left-hand column. This drive voltage
adjusts the rotational speed of the blower to
maximize combustion efficiency.
Permits selection of the Air/Fuel Valve position (%
open) to be set from 0 to 100%.
Permits the DC drive voltage to the blower to be
monitored.
Permits the Standby Voltage to be set from 0 to
4.00 Volts.
Permits the combustion oxygen level to be
displayed (0% to 25%)
DESCRIPTION
Displays the default DC drive voltage provided to
the blower at each of the Air/Fuel Valve positions
show in the left-hand column. This drive voltage
adjusts the rotational speed of the blower to
maximize combustion efficiency.
Permits selection of the Air/Fuel Valve position (%
open) to be set from 0 to 100%.
Permits the DC drive voltage to the blower to be
monitored.
Permits the Standby Voltage to be set from 0 to
4.00 Volts.
Permits the combustion oxygen level to be
displayed (0% to 25%)
Page 145 of 234