Operating Menu; Setup Menu - Aerco BENCHMARK 2500DF User Manual

Dual fuel gas-fired boiler
Table of Contents

Advertisement

Benchmark 2500DF-3000DF Installation, Operation & Maintenance Manual

3.4 OPERATING MENU

The Operating Menu displays a number of key operating parameters for the unit as listed in Table 3-2.
This menu is "Read-Only" and does not allow personnel to change or adjust any displayed items. Since
this menu is "Read-Only", it can be viewed at any time without entering a password. Pressing the ▲
arrow key to display the menu items in the order listed (Top-Down). Pressing the ▼ arrow key will display
the menu items in reverse order (Bottom-Up).
Menu Item Display
Active Setpoint
Inlet Temp
Air Temp
Outdoor Temp*
Valve Position In
Valve Position Out*
Exhaust Temp
Flame Strength
Oxygen Level
Run Cycles
Run Hours
Fault Log
The Outdoor Temp and Valve Position Out display items shown
with an asterisk in Table 3-2 will not be displayed unless the
Outdoor Sensor function has been enabled in the Configuration
Menu (Table 3-4).

3.5 SETUP MENU

The Setup Menu (Table 3-3) permits the operator to enter the unit password (159) which is required to
change the menu options.
Therefore, the correct password must be reentered when required. In addition to permitting password
entries, the Setup Menu is also used to enter date and time, units of temperature measurements and
entries required for external communication and control of the unit via the RS-232 port. A view-only
software version display is also provided to indicate the current Control Box software version.
OMM-0099_0A
GF-145
CHAPTER 3 – OPERATION
Table 3-2: Operating Menu
Available Choices or Limits
Minimum
40°F
40°F
-70°F
-70°F
0%
0%
°F
0%
0%
0
0
0
*NOTE
To prevent unauthorized use, the password will time-out after 1 hour.
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Ph.: 800-526-0288
Default
Maximum
240°F
140°F
245°F
130°F
100%
100%
°F
100%
21%
999,999,999
999,999,999
19
0
Page 39 of 234
PR1: 05/21/2014

Advertisement

Table of Contents
loading

This manual is also suitable for:

Benchmark 3000df

Table of Contents