Page 1
BMK 3000 • Applies to Serial Numbers: G-17-2400 and above. U.S. Patent #: 9,243,848 Korea Patent #: 10-1755141 Latest Update: 11/29/2017 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 1 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
FORWARD FOREWORD The AERCO Benchmark (BMK) 750, 1000, 1500, 2000, 2500, and 3000 natural gas fueled boilers are modulating and condensing units. They represent a true industry advance that meets the needs of today's energy and environmental concerns. Designed for application in any closed loop hydronic system, the Benchmark's modulating capability relates energy input directly to fluctuating system loads.
Page 6
BTUs per Hour (1 BTU/hr = 0.29 W) Combination Control Panel Combination Control System A control system developed by AERCO and currently used in all C-More Controller Benchmark, Innovation and KC1000 Series product lines. Cubic Feet per Hour (1 CFH = 0.028 m...
Page 7
Part Number Proof of Closure Parts per Million Pounds per Square Inch (1 PSI = 6.89 kPa) Point-to-Point (usually over RS232 networks) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 7 of 146 Ph.: 800-526-0288 GF-206-K...
Page 8
W.C. Water Column, a unit of pressure (1 inch W.C. = 249 Pa) µA Micro amp (1 million of an ampere) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 8 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017...
In addition to all the requirements included in this AERCO Instruction Manual, the installation of units MUST conform with local building codes, or, in the absence of local codes, ANSI Z223.1 (National Fuel Gas Code Publication No. NFPA-54) for gas-fired boilers.
Installation and Startup Guide Guide, OMM-0127 (GF-205-K) be performed to verify all system- operating parameters. If there is an emergency, turn off the electrical power supply to the AERCO boiler and close the manual gas valve located upstream the unit. The installer must identify the emergency shut-off device.
All of the installation procedures in the Benchmark 750 – 3000 Boiler Installation and Startup Guide, OMM-0127 (GF-205-K) must be completed before attempting to start the unit. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 11 of 146 Ph.: 800-526-0288...
Additional information on these items is provided in the individual operating procedures and menu descriptions provided in this section. Figure 2-1: C-More Controller Front View AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 12 of 146 OMM-0128_0C Ph.: 800-526-0288...
Page 13
• Pressing RESET resets the water level monitor circuit. switches • Pressing the CLEAR key (item 6) resets the display. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 13 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Page 14
20 segment red LED bargraph continuously shows the Air/Fuel VALVE POSITION Valve position in 5% increments from 0 to 100% Bargraph AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 14 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017...
The menu option choices do not wrap around. 7. To select and store a changed menu item, press the ENTER key. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 15 of 146 Ph.: 800-526-0288...
Page 16
Refer to Appendix A for detailed descriptions of each menu option. Refer to Appendix B for a list and descriptions of startup, status and error messages. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 16 of 146 OMM-0128_0C Ph.: 800-526-0288...
An additional parameter associated with the Operating menu, Manual Valve Pos (Min = 0, Max = 100) does not appear in this menu, but can be displayed by pushing the Auto/Man button on the C-More Controller’s front face. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 17 of 146 Ph.: 800-526-0288...
E, G, H, R, N or A Unit Year Unit Serial # 9999 Current software Software Ver 0.00 Ver 9.99 version AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 18 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
100°F 60°F (If Outdoor Sensor = (-1.1°C) (37.8°C) (15.6°C) Enabled) Setpt Lo Limit 40°F (4.4°C) Setpt Hi Limit 60°F (15.6°C) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 19 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Page 20
Sensor, item # 7 is set to Enabled. CAUTION! DO NOT change the Analog Output menu item from its default setting (Valve Position 0- 10V). AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 20 of 146 OMM-0128_0C Ph.: 800-526-0288...
5.60 SET Valve Position 100% Blower Output Monitor Blower Output Voltage 0.00 Set Stdby Volt 10.0 V 2.00 Oxygen Level AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 21 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Variable Blower Output Displays current value Set Stdby Volt 10.00 V 2.00 V 2.00 V Oxygen Level Displays current value AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 22 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
Constant Remote Outdoor BST Setpoint Mode Constant Setpt Setpoint Setpoint Reset 4-20 mA/1-5 0-20 mA/0-5 BST Remote Signl Network Network AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 23 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Page 24
225 hours 72 hours 44 *TEMP CTRL MENU* Disabled Enabled Disabled BST Temp Hi Limit 40°F (4.4°C) 210°F (98.9°C) 210°F (98.9°C) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 24 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
Page 25
Unit 2 is Off Unit 4 is Not Available Unit 5 is Lead On Unit 6 is Lag Off 1 BST Units 8 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 25 of 146 Ph.: 800-526-0288 GF-206-K...
-1.0 mA 1.0 mA 0.0 mA A/F Sensitivity Power Reset Automatic or Manual Automatic Water Temp Reset Automatic or Manual Automatic AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 26 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
Page 27
Depends on unit type/size Min Spark Amps 0.0 Amps 2.5 Amps 0.10 Amps Max Spark Amps 0.0 Amps 2.5 Amps 0.40 Amps AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 27 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Page 28
Benchmark 750-3000 Boiler Operation, Service, Maintenance Guide - KOREA SECTION 2: OPERATION (This page intentionally blank) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 28 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
I/O Box. Refer to Section 2.10: AC Electrical Power Wiring of the Benchmark 750 – 3000 Boiler Installation and Startup Guide Guide, OMM-0127 (GF-205-K) for additional information on wiring. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 29 of 146 Ph.: 800-526-0288...
The unit is factory preset with settings that work well in most applications. Prior to changing any temperature-related parameters, other than the setpoint, it is suggested that an AERCO representative be contacted. See Appendix A for descriptions of temperature-related functions, and Sections 2.4 – 2.10 for their range of values and factory defaults.
Remote Setpoint Remote Signal 4-20mA/1-5V, 0-20mA/0-5V, or Network Refer to Section 2.3: C-More Controller Menus for detailed instructions on changing menu options. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 31 of 146 Ph.: 800-526-0288 GF-206-K...
While it is possible to change the settings of temperature related functions, the unit is factory preset with settings that work well in most applications. It is suggested that an AERCO representative be contacted, prior to changing any temperature related function settings. See Appendix A for descriptions of temperature-related functions, and Sections 2.4 –...
To change back to the Direct Drive mode, simply press the AUTO/MAN switch. The REMOTE LED will again light and the MANUAL LED will go off. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 33 of 146 Ph.: 800-526-0288...
Section 6 of the Benchmark 750 – 3000 Boiler Installation and Startup Guide Guide, OMM- 0127 (GF-205-K). The ACS mode of operation is used in conjunction with an AERCO Control System. The ACS mode is used when it is desired to operate multiple units in the most efficient manner possible.
Only the AERCO Control System (ACS) is necessary to configure this system if only a single valve is used to switch from space heating to domestic hot water. However, the ACS Relay...
These default settings work well in most applications. It is suggested that AERCO be contacted prior to changing settings other than the unit’s setpoint. For a complete listing of temperature related function defaults, see Sections 2.4 –...
For best operation and life of the unit, the following routine maintenance procedures should be performed in the time periods specified in Table 4-1. For a complete inspection check list see ASME CSD-1 chart. The following maintenance kits are available through your local AERCO Sales Representative: Model Kit P/N...
Page 41
Reconnect the igniter-injector cable. Reinstall the shroud on the unit. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 41 of 146 Ph.: 800-526-0288...
Page 42
POSITION O2 SENSOR INJECTOR TUBE INSIDE THIS ARC FLAME OBSERVATION INJECTOR TUBE PORT IGNITER-INJECTOR Figure 4-3c. BMK 2500/3000 Igniter-Injector Orientation AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 42 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
6. Reinstall the O sensor and crush washer on the burner plate. 7. Reconnect the sensor lead wire. Reinstall the shroud on the unit. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 43 of 146 Ph.: 800-526-0288...
(see Figure 4-1a, below). Disconnect the staged ignition assembly from the igniter-injector. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 44 of 146 OMM-0128_0C Ph.: 800-526-0288...
Page 45
Figure 4-4b: BMK 750/1000 Burner Assembly (Exploded View) 8. Next, loosen and remove the igniter-injector from the burner plate using a 1" open-end wrench. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 45 of 146 Ph.: 800-526-0288...
Page 46
19. Ensure that the igniter-injector and flame detector cutouts in the burner plate are properly aligned with the heat exchanger top flange. This completes the Benchmark 750/1000 burner inspection. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 46 of 146 OMM-0128_0C Ph.: 800-526-0288...
BURNER PLATE A/F VALVE PLENUM 1/2” NUTS & BOLTS (4 ea.) FILTER Figure 4-5a: BMK 1500/2000 Burner Assembly Mounting Details AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 47 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Page 48
1/2” NUTS (8 each) & BOLTS (4 each) AIR FILTER GAS TRAIN Figure 4-5c: BMK 2500/3000 Burner Assembly Mounting Details AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 48 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
Page 49
9. Loosen and remove the four 5/16 x 1-3/4” bolts, washers, and nuts from the blower plenum where it attaches to the blower. See Figure 4-5a & 4-5b (BMK 1500/2000) or Figures 4-5c & 4-5d (BMK 2500/3000). AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 49 of 146 Ph.: 800-526-0288...
Page 50
Nm). 16. Ensure that the igniter-injector and flame detector cutouts in the burner plate are properly aligned with the heat exchanger top flange. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 50 of 146 OMM-0128_0C Ph.: 800-526-0288...
4. Using a flat-tip screwdriver or 5/16” nut driver, loosen the clamp securing the filter to the inlet flange of the air/fuel valve. Remove the filter and clamp. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 52 of 146 OMM-0128_0C Ph.: 800-526-0288...
5. Perform scheduled maintenance procedures per Section 4 of this manual and safety device testing per Section 5 of the Benchmark 750 – 3000 Boiler Installation and Startup Guide Guide, OMM-0127 (GF-205-K). AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 55 of 146 Ph.: 800-526-0288...
I/O board’s Spark Signal terminals, red wire to the positive (+) terminal and black to negative (-). AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 56 of 146 OMM-0128_0C Ph.: 800-526-0288...
The front panel of the C-More Controller contains an RS232 port. This port is used only by factory-trained personnel to monitor onAER communications via a portable computer. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 57 of 146 Ph.: 800-526-0288...
Page 58
Benchmark 750-3000 Boiler Operation, Service, Maintenance Guide - KOREA SECTION 5 – TROUBLESHOOTING GUIDE (This page intentionally blank) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 58 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
Page 59
Air/Fuel Valve dial. Hard light. Check igniter-injector for soot or erosion of electrode. Check injector solenoid valve to insure proper open/close operation. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 59 of 146 Ph.: 800-526-0288...
Page 60
Probable causes from 3 to 16 for AIRFLOW See CORRECTIVE ACTIONS from 3 to 12 for AIRFLOW FAULT FAULT DURING IGNITION applies for this fault. DURING IGNITION. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 60 of 146 OMM-0128_0C Ph.: 800-526-0288...
Page 61
120VAC at the valve input terminals. If 120VAC is not present, the IGST board in the C-More Controller may be defective. Refer fault to qualified service personnel. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 61 of 146 Ph.: 800-526-0288...
Page 62
(C) and normally closed (NC) Defective High Gas Pressure switch. terminals with the unit not firing. Replace the switch if continuity does not exist. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 62 of 146 OMM-0128_0C Ph.: 800-526-0288...
Page 63
Press CLEAR button and restart unit. If fault persists, contact Communication fault has occurred between the IGN BOARD PMC board and Ignition/Stepper (IGST) board. qualified Service Personnel. COMM FAULT AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 63 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Page 64
Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF Defective IGST Board. every second. If not, replace IGST Board. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 64 of 146 OMM-0128_0C Ph.: 800-526-0288...
Page 65
MODBUS Check network connections. If fault persists, contact qualified Unit not seeing information from Modbus network. COMMFAULT Service Personnel. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 65 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Page 66
Check resistance of sensor to determine if it is within specification. SENSOR Incorrect Sensor. Ensure that the correct sensor is installed. FAULT AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 66 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017...
Page 67
SSOV switch closed for 15 seconds during run. Replace or adjust micro-switch in SSOV actuator. If fault persists, SSOV FAULT replace actuator. DURING RUN AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 67 of 146 Ph.: 800-526-0288 GF-206-K...
Page 68
Defective IGST Board. Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF every second. If not, replace IGST Board. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 68 of 146 OMM-0128_0C Ph.: 800-526-0288...
Check to ensure that the IGST and Power Supply Boards are Rev. E Air/Fuel Valve “hunting” at in C-More Controller are or higher. the 70% Valve Position outdated. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 69 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Page 70
BRASS HEX HEAD (Remove to access the Gas Pressure Adjustment Screw). COVER SCREW Figure 5-1: SSOV Actuator With Gas Pressure Adjustment (SKP25) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 70 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
Displays the current going to the ignition transformer. Run Cycles Displays the total number of run cycles. Run Hours Displays total run time of unit in hours. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 71 of 146 Ph.: 800-526-0288 GF-206-K...
Page 72
An additional parameter associated with the Operating menu, Manual Valve Pos (Min = 0, Max = 100) does not appear in this menu, but can be displayed by pushing the Auto/Man button on the C-More Controller’s front face. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 72 of 146 OMM-0128_0C Ph.: 800-526-0288...
4-digit serial # on the Code Plate, e.g., G-12- Software Version Identifies the current software version of the C-More Controller. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 73 of 146 Ph.: 800-526-0288...
Setpt Hi Limit. Used to set the maximum allowable setpoint, from the Setpt Lo Setpt Hi Limit Limit up to 210°F (98.9 °C) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 74 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017...
Page 75
Valve Position In reaches the Start Level value (Calibration menu item 37). There will not be a one minute delay when firing at the 29% Valve Position level. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 75 of 146 Ph.: 800-526-0288...
Page 76
When set to Enabled, the AERtrim menu options appears. O2 Trim Menu BST Menu When set to Enabled, the BST menu options appears. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 76 of 146 OMM-0128_0C Ph.: 800-526-0288...
Range = 0 - 240 seconds Default = 20 seconds Timer Allows Tuning menu options to be reset to their Factory Reset Defaults? Default values. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 77 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Permits the Standby Voltage to be set from 0 to 4.00 Set Stby V out Volts. Permits the combustion oxygen level to be displayed Oxygen Level (0% to 25%) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 78 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
Allows adjustment of the analog input from -5.0% to +5.0%. Allows adjustment of the water Flow Rate Input from Flow In Adj -5.0% to +5.0%. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 79 of 146 Ph.: 800-526-0288...
Page 80
– FFWD Temp Offset Range: -20 to + 20 (either ºF or °C) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 80 of 146 OMM-0128_0C Ph.: 800-526-0288...
Page 81
Allows the adjustment of the maximum spark current required at Max Spark Amps the spark transformer input. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 81 of 146 Ph.: 800-526-0288 GF-206-K...
Page 82
Benchmark 750-3000 Boiler Operation, Service, Maintenance Guide - KOREA APPENDIX A: BOILER MENU DESCRIPTIONS (This page intentionally blank) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 82 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
The time and date are also displayed. Prompts the operator to wait. WAIT WARMUP Displayed for 2 minutes during the initial warm-up only. XX sec AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 83 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
The Low Water Cutoff board is indicating low water level. LEVEL NETWORK COMM The RS-485 network information is not present or is corrupted. FAULT AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 84 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017...
Page 85
A failure has been detected in one of the relays that control the SSOV. FAILURE STEPPER MOTOR The Stepper Motor failed to move the Air/Fuel Valve to the desired position. FAILURE AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 85 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Page 86
Benchmark 750-3000 Boiler Operation, Service, Maintenance Guide - KOREA APPENDIX B – STARTUP, STATUS, AND FAULT MESSAGES (This page intentionally blank) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 86 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017...
Startup Guide Guide, OMM-0127 (GF- 205-K). Check flame strength using the C-More Flame signal strength Weekly Operator Controller’s Operating menu (see Section 2.4). AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 89 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Page 90
See Section 4.7. Annually Verify oxygen level is between 3% and 8% Oxygen (O ) Level Monthly Operator during boiler operation. AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 90 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
Inc. Blauvelt, NY Benchmark 750 P/N 28321-TAB rev F 10913 Sheet 1 of 6 Benchmark 1000 P/N 28253-TAB rev F AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 95 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Page 96
Inc. Blauvelt, NY Benchmark 750 P/N 28321-TAB rev F 10913 Sheet 2 of 6 Benchmark 1000 P/N 28253-TAB rev F AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 96 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
Page 97
Inc. Blauvelt, NY Benchmark 750 P/N 28321-TAB rev F 10913 Sheet 3 of 6 Benchmark 1000 P/N 28253-TAB rev F AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 97 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Page 98
Inc. Blauvelt, NY Benchmark 750 P/N 28321-TAB rev F 10913 Sheet 4 of 6 Benchmark 1000 P/N 28253-TAB rev F AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 98 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
Page 99
Inc. Blauvelt, NY Benchmark 750 P/N 28321-TAB rev F 10913 Sheet 5 of 6 Benchmark 1000 P/N 28253-TAB rev F AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 99 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Page 100
Inc. Blauvelt, NY Benchmark 750 P/N 28321-TAB rev F 10913 Sheet 6 of 6 Benchmark 1000 P/N 28253-TAB rev F AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 100 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
Page 101
DAMPING ORIFICE: SSOV Benchmark 750/1000 FM Gas Train AERCO International, 04/11/2017 Inc. Blauvelt, NY 10913 22140-1 rev G Sheet 1 of 1 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 101 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Page 102
A/F VALVE ASSY BMK 750 AERCO International, Benchmark 750/1000 Burner Assembly 08/15/2017 Inc. Blauvelt, NY 10913 24276-TAB Rev K Sheet 1 of 1 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 102 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
AERCO International, Inc. Benchmark 1500 29313-TAB rev G Blauvelt, NY 10913 Sheet 1 of 7 Benchmark 2000 29337-TAB rev G AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 103 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Page 104
AERCO International, Inc. Benchmark 1500 29313-TAB rev G Blauvelt, NY 10913 Sheet 2 of 7 Benchmark 2000 29337-TAB rev G AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 104 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
Page 105
AERCO International, Inc. Benchmark 1500 29313-TAB rev G Blauvelt, NY 10913 Sheet 3 of 7 Benchmark 2000 29337-TAB rev G AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 105 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Page 106
AERCO International, Inc. Benchmark 1500 29313-TAB rev G Blauvelt, NY 10913 Sheet 4 of 7 Benchmark 2000 29337-TAB rev G AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 106 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
Page 107
AERCO International, Inc. Benchmark 1500 29313-TAB rev G Blauvelt, NY 10913 Sheet 5 of 7 Benchmark 2000 29337-TAB rev G AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 107 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Page 108
AERCO International, Inc. Benchmark 1500 29313-TAB rev G Blauvelt, NY 10913 Sheet 6 of 7 Benchmark 2000 29337-TAB rev G AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 108 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
Page 109
AERCO International, Inc. Benchmark 1500 29313-TAB rev G Blauvelt, NY 10913 Sheet 7 of 7 Benchmark 2000 29337-TAB rev G AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 109 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Page 110
TUBING: FLEXIBLE 16" Benchmark 1500/2000 Gas Train AERCO 04/17/2017 International, Inc. Blauvelt, NY 10913 P/N 22240 rev D Sheet 1 of 2 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 110 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
Page 111
APPENDIX G – BENCHMARK 1500/2000 PART LISTS AERCO Benchmark 1500/2000 Gas Train 04/17/2017 International, Inc. P/N 22240 rev D Blauvelt, NY 10913 Sheet 2 of 2 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 111 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Page 112
61024 60011-2 Benchmark 1500/2000 Burner Assembly AERCO 08/09/2017 International, Inc. Blauvelt, NY 10913 24378-TAB rev G Sheet 1 of 1 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 112 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
AERCO International, Inc. Blauvelt, NY Benchmark 2500 28536-TAB rev E 10913 Sheet 1 of 8 Benchmark 3000 28382-TAB rev F AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 113 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Page 114
AERCO International, Inc. Blauvelt, NY Benchmark 2500 28536-TAB rev E 10913 Sheet 2 of 8 Benchmark 3000 28382-TAB rev F AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 114 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
Page 115
AERCO International, Inc. Benchmark 2500 28536-TAB rev E Blauvelt, NY 10913 Sheet 3 of 8 Benchmark 3000 28382-TAB rev F AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 115 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Page 116
AERCO International, Inc. Blauvelt, NY Benchmark 2500 28536-TAB rev E 10913 Sheet 4 of 8 Benchmark 3000 28382-TAB rev F AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 116 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
Page 117
AERCO International, Inc. Benchmark 2500 28536-TAB rev E Blauvelt, NY 10913 Sheet 5 of 8 Benchmark 3000 28382-TAB rev F AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 117 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Page 118
AERCO International, Inc. Blauvelt, NY Benchmark 2500 28536-TAB rev E 10913 Sheet 6 of 8 Benchmark 3000 28382-TAB rev F AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 118 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
Page 119
AERCO International, Inc. Benchmark 2500 28536-TAB rev E Blauvelt, NY 10913 Sheet 7 of 8 Benchmark 3000 28382-TAB rev F AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 119 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Page 120
AERCO International, Inc. Benchmark 2500 28536-TAB rev E Blauvelt, NY 10913 Sheet 8 of 8 Benchmark 3000 28382-TAB rev F AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 120 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
Page 121
TUBING: FLEXIBLE 26" AERCO Benchmark 2500 Gas Train 04/17/2017 International, Inc. Blauvelt, NY 10913 P/N 22244 rev F Sheet 1 of 2 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 121 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Page 122
APPENDIX H – BENCHMARK 2500/3000 PART LIST AERCO Benchmark 2500 Gas Train 04/17/2017 International, Inc. P/N 22244 rev F Blauvelt, NY 10913 Sheet 2 of 2 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 122 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
Page 123
GAGE: LOW PRESSURE 0-10 in./H2O AERCO Benchmark 3000 Gas Train 04/17/2017 International, Inc. P/N 22215 rev H Blauvelt, NY 10913 Sheet 1 of 2 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 123 of 146 Ph.: 800-526-0288 GF-206-K 11/29/2017...
Page 124
APPENDIX H – BENCHMARK 2500/3000 PART LIST AERCO Benchmark 3000 Gas Train 04/17/2017 International, Inc. P/N 22215 rev H Blauvelt, NY 10913 Sheet 2 of 2 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 124 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...
Page 125
International, Inc. BMK 2500 – 26015-TAB rev E Blauvelt, NY 10913 Sheet 1 of 1 BMK 3000 – 26014-TAB rev K AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0128_0C Page 125 of 146 Ph.: 800-526-0288 GF-206-K...
Page 126
Benchmark 750-3000 Boiler Operation, Service, Maintenance Guide - KOREA APPENDIX H – BENCHMARK 2500/3000 PART LIST (This page intentionally blank) AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 Page 126 of 146 OMM-0128_0C Ph.: 800-526-0288 11/29/2017 GF-206-K...