Benchmark 2500DF-3000DF Installation, Operation & Maintenance Manual
FAULT INDICATION
(continued)
FLAME LOSS
DURING RUN
HEAT DEMAND
FAILURE
HIGH EXHAUST
TEMPERATURE
Page 108 of 234
05/21/2014
CHAPTER 8 – TROUBLESHOOTING GUIDE
TABLE 8-1: BOILER TROUBLESHOOTING – Continued
PROBABLE CAUSES
6. Carbon or other debris on Burner.
7. Staged ignition solenoid valve
doesn't open.
8. Clogged staged ignition piece.
1. Worn Flame Detector or cracked
ceramic.
2. Defective Regulator.
3. Poor combustion calibration.
4. Debris on burner.
5. Blocked condensate drain.
1. The Heat Demand Relays on the
Ignition/Stepper (IGST) board failed
to activate when commanded.
2. Relay is activated when not in
Demand.
1. Poor combustion calibration.
2. Carboned heat exchanger due to
incorrect combustion calibration
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Phone: 800-526-0288
CORRECTIVE ACTION
6. Remove View-Port and inspect Burner with Boroscope. If it is fouled
or black with soot, remove the Burner and inspect for any carbon
build-up or debris. Clean and reinstall.
7. When unit goes to ignition, listen for a clicking sound at the staged
ignition solenoid valve to ensure it is opening.
8. Remove and inspect staged ignition piece for blockage.
1. Remove and inspect the Flame Detector for signs of wear or
cracked ceramic. Replace if necessary.
2. Check gas pressure readings using a gauge or manometer into and
out of the Air/Fuel Valve to ensure that the gas pressure into and
out of the valve is correct.
3. Check combustion calibration using procedures in Chapter 4.
4. Remove the burner and inspect for any carbon build-up or debris.
Clean and reinstall.
5. Remove blockage in condensate drain.
1. Press CLEAR button and restart the unit. If the fault persists,
replace Ignition/Stepper (IGST) Board.
2. Defective relay. Replace IGST Board.
1. Check combustion calibration using procedures in Chapter 4.
2. If exhaust temperature is greater than 200
calibration. Calibrate or repair as necessary.
o
F, check combustion
OMM-0099_0A
GF-145