Aerco BENCHMARK 2500DF User Manual page 140

Dual fuel gas-fired boiler
Table of Contents

Advertisement

Benchmark 2500DF-3000DF Installation, Operation & Maintenance Manual
Table A-1: Boiler Menu Item Descriptions – Continued
MENU LEVEL & OPTION
Password
Language
Time
Date
Unit of Temp
Comm Address
Baud Rate
Min Upload Timer
Unit Alpha
Unit Year
Unit Serial #
Software Version
Internal Setpoint
Unit Type
Page 140 of 234
05/21/2014
APPENDIX A – BOILER MENU ITEM DESCRIPTIONS
SETUP MENU
Allows Level 1 or Level 2 password to be entered.
Entering the Level 1 Password (159) allows options in the
Setup, Configuration and Tuning Menus to be modified.
Entering the Level 2 Password (6817) allows options in the
Calibration and Diagnostics Menus to be changed or
activated, in addition to all Level 1 Menu options.
Permits selection of English, Spanish or French for
displayed messages. Default is English.
Displays time from 12:00 am to 11:59 pm.
Displays dates from 01/01/00 to 12/31/99
Permits selection of temperature displays in degrees
Fahrenheit (°F) or degrees Celsius (°C). Default is °F.
For RS-485 communications (0 to 127). Default address is
0. RS-232 should have its own (programmable) password.
Allows communications Baud Rate to be set (2400 to
19.2K). Default is 9600.
Mandatory for AERCO OnAER Remote Data Collection
(ORDC). This parameter enables ORDC and defines the
minimum amount of time between heartbeat data uploads in
seconds. The COMM LED will light during the upload.
Mandatory for AERCO OnAER Remote Data Collection.
This value must match the first alpha digit on the Code
Plate, e.g., G-12-1234.
Mandatory for AERCO OnAER Remote Data Collection.
This value must match the 2-digit year on the Code Plate,
e.g., G-12-1234.
Mandatory for AERCO OnAER. Remote Data Collection.
This value must match the 4-digit serial # on the Code
Plate, e.g., G-12-1234.
Identifies the current software version of the control box
(Ver 0.0 to Ver 9.9).
Allows internal setpoint to be set. Default is 130°F.
Allows selection of KC Boiler, KC Boiler LN, BMK Boiler
Std, BMK Blr Std Dual, BMK Boiler LN, BMK Blr LN Dual,
KC Water Heater, KC Wtr Heater LN, Innovation WH
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Phone: 800-526-0288
DESCRIPTION
OMM-0099_0A
GF-145

Advertisement

Table of Contents
loading

This manual is also suitable for:

Benchmark 3000df

Table of Contents