Application planning
4.2 Location planning
4.2.5

Electrical installation

• Low voltage:
The Dispenser is designed for the connection to the low-voltage network (230 V AC) via
the charging station. Connect the Dispenser to the SICHARGE UC charging station using a
properly dimensioned supply cable.
• Direct voltage:
The Dispenser is designed for the connection of direct voltage to a SICHARGE UC charging
station. Connect the Dispenser using a properly dimensioned cable.
NOTE
Routing of DC cables to prevent radio interference
Route the DC charging cables underground from the charging station to the Dispenser or
attach the cables to the floor. We recommend using shielded cables when routing cables
above ground to reduce the electromagnetic radiation of the cables. Further measures
may be required in the event of interference with the radio spectrum. Measures include,
for example, the use of EMC filters or ferrites, which are then mounted at the output of
the DC charging cable.
• Ethernet:
Connect the SICHARGE UC Dispenser and the SICHARGE UC charging station with an
Ethernet cable.
Specifications for cable routing:
– Low-voltage and DC cables must be installed shielded from the Ethernet cable.
– Separate cable routing to low-voltage and DC cables (min. 20 cm).
– Lay Ethernet cable close to grounded cabinet components.
– Ethernet cables, low-voltage and DC cables may only cross each other at a 90° angle.
– Ground the shielding of the Ethernet cable at both cable ends.
NOTE
Installer is responsible for the calculation and design
The installer is responsible for calculating and implementing the connection.
Connection of the charging station must comply with standards and regulations.