Application planning
4.4 Preparing the mounting surface
Cable lengths
The following table shows the cable lengths from the screw connections up to the terminals
in the Dispenser.
Table 4-2 Min. cable lengths Dispenser wall / ceiling installation
Description
230 V AC AUX supply
Global DC shutdown loop
750 V DC connection
750 V DC connection
Protective conductor
Communication
Drill holes for fixing points on the wall/ceiling
To fasten the Dispenser, the following drill holes must be available for the fixing points:
Figure 4-14 Fastening for wall/ceiling mounting
Fastening to the wall/ceiling
The mounting material is not included in the scope of delivery.
We recommend the following fixing accessories for mounting the Dispenser to the
wall/ceiling:
• Concrete wall:
– 4 bolt anchors M12
– 4 washers M12
– 4 nuts M12
– Bolt lock adhesive
• Other wall types:
– Approved mounting material with 12 mm screws/bolts
– Matching accessories for the selected mounting material
54
L/N/PE
L+
L-
PE
Min. cable length in the Dispenser
0.7 m
1 m
0.4 m
0.4 m
0.2 m
1 m
Operating Instructions, 07/2023, A5E52329862-AB
Dispenser