10
Maintenance
CAUTION
Risk of burns
Escaping hot medium can cause burns.
•
Maintain a sufficient distance from the escaping medium.
•
Wear suitable personal protective equipment (safety gloves and goggles).
DANGER
Risk of serious injury or death due to electric shock.
If live parts are touched, there is risk of life-threatening injuries.
•
Ensure that the system is voltage-free before installing the device.
•
Ensure that the system is secured and cannot be reactivated by other persons.
•
Ensure that installation work for the electric connection of the device is carried out by an electrician, and in compliance with
electrical engineering regulations.
The device is to be maintained annually.
–
The maintenance intervals depend on the operating conditions and the degassing times.
The annual maintenance is displayed upon expiry of the set operating time. Use "Quit" to acknowledge the "Maintenance
recommended" message. Reset the maintenance counter in the Customer menu.
Notice!
Maintenance work must be carried out and confirmed by specialist personnel or the Reflex Customer Service, see
chapter 10.4 "Maintenance certificate " on page 52 .
10.1
Maintenance schedule
The maintenance schedule is a summary of maintenance tasks to be carried out regularly.
Maintenance task
▲ = Check, ■ = Service, ● = Clean
Check for leaks.
•
"CO" compressor.
•
Screw connections of the compressed air connections.
Check switching points.
•
"CO" compressor cut-in pressure.
•
Insufficient water.
•
Make-up with water.
Clean "ST" dirt trap.
–
see chapter 10.3.2 "Cleaning the dirt trap" on page 51 .
Remove condensate from the primary tank and the secondary tanks, if
applicable.
–
see chapter 10.3.1 "Cleaning the tanks" on page 50 .
Reflexomat with Basic controller — 20.06.2017 - Rev. C
Conditions
Interval
▲
■
▲
Depending on the operating
●
▲
■
●
▲
■
Maintenance
Annually
Annually
conditions
Annually
English — 47
Need help?
Do you have a question about the Reflexomat Compact RC Series and is the answer not in the manual?
Questions and answers