Configuring Settings In The Controller - Reflex Reflexomat Compact RC Series Operating Manual

Table of Contents

Advertisement

9.2

Configuring settings in the controller

You can configure the controller settings regardless of the currently selected and active operating mode.
Use the Customer menu to display or correct system-specific values. In the course of commissioning, the factory settings must be
adjusted for the system-specific conditions.
Notice!
Operation description, see chapter 9.1 "Operator panel" on page 38 .
All grey marked menu items must be reviewed during commissioning.
Press "Manual" to switch to manual operation.
Press "Menu" to display the first main menu option "Customer menu".
Switch to the next main menu option.
Standard software with various languages.
Adjust the "Hour", "Minute", and "Second" display when each begins to flash.
This time is used for entries in the fault memory.
Adjust the "Day", "Month", and "Year" display when each begins to flash.
This date is used for entries in the fault memory.
The controller checks whether the level sensor signal matches the value entered for the
"RG" primary tank in the controller, see chapter 7.3 "Modifying the controller's start
routine" on page 34 .
Notice!
The "RG" primary tank must be completely empty.
One of the following messages appears on the display:
Null balancing concluded successfully.
Confirm with the "▼" button.
Empty the tank and repeat the process.
Confirm with "OK".
This message appears when null balancing has failed. Select "Yes" or "No" on the display.
Yes:
The "RG" primary tank is empty and the device is installed as per the instructions. If
null balancing is still not possible, cancel with "Yes". Contact your Reflex Customer
Service.
No:
Check the prerequisites for the commissioning, see chapter 7.1 "Checking the
requirements for commissioning" on page 32 .
The controller's start routine is restarted.
Confirm the selection of "Yes" or "No" with "OK".
Reflexomat with Basic controller — 20.06.2017 - Rev. C
Customer menu
Language
Time:
Date:
1 %
1.7 bar
Null balancing?
0 %
0 bar
Null balancing concluded
successfully!
0 %
0 bar
Cancel null balancing
English — 39
Controller