Commissioning
7.3

Modifying the controller's start routine

Note!
During commissioning, you must once execute the start routine.
For information about controller operation, see chapter 9.1 "Operator panel" on page 38 .
The start routine is used to set the required parameters for the device commissioning. It commences with the first activation of the
controller and can be run only once. Parameters can be changed or checked in the customer menu after the start routine has terminated.
Notice!
Plug in the contact plug to provide power (230 V) to the controller.
You are now in Stop mode. The "Auto" LED on the operator panel has extinguished.
Device name
Standard software with various languages.
Prior to commissioning, read the entire operating manual and verify the proper assembly.
Enter the value for the minimum operating pressure.
Calculating the minimum operating pressure, see chapter 7.2 "Determining the P
minimum operating pressure for the controller" on page 33 .
Change the flashing display items for "Hour", "Minute", and "Seconds" to the current time.
The time of an alarm will be stored in the fault memory.
Change the flashing display items for "Day", "Month", and "Year" to the current date.
The date of an alarm will be stored in the fault memory.
Select the size of the primary tank.
For the primary tank data, see the name plate or see chapter 5 "Technical data" on
page 15 .
34 — English
Reflexomat with Basic controller — 20.06.2017 - Rev. C
Reflexomat
Language
Read the operating manual!
Min. op. pressure
0
Time
Date
00500 l
740 mm
GB = 0093 kg