ABB RELION 670 Series Applications Manual page 369

Busbar protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 505 337-UUS A
If the IED is connected to a station bus (IEC 61850-8-1), the disturbance recorder (record made and
fault number) and the fault locator information are available as GOOSE or Report Control data. The
same information is obtainable if IEC60870-5-103 is used.
14.6.3
Setting guidelines
The setting parameters for the Disturbance report function DRPRDRE are set via the local HMI or
PCM600.
It is possible to handle up to 40 analog and 352 binary signals, either internal signals or signals
coming from external inputs. The binary signals are identical in all functions that is, Disturbance
recorder (DR), Event recorder (ER), Indication (IND), Trip value recorder (TVR) and Sequential of
events (SOE) function.
User-defined names of binary and analog input signals is set using PCM600. The analog and binary
signals appear with their user-defined names. The name is used in all related functions
(Disturbance recorder (DR), Event recorder (ER), Indication (IND), Trip value recorder (TVR) and
Sequential of events (SOE)).
Figure
180
blocks. Sequential of events (SOE), Event recorder (ER) and Indication (IND) uses information from
the binary input function blocks (BxRBDR). Trip value recorder (TVR) uses analog information from
the analog input function blocks (AxRADR),. Disturbance report function acquires information
from both AxRADR and BxRBDR.
Figure 180: Disturbance report functions and related function blocks
For Disturbance report function there are a number of settings which also influences the sub-
functions.
Three LED indications placed above the LCD screen makes it possible to get quick status
information about the IED.
Green LED:
Steady light
Flashing light
Dark
Yellow LED:
Steady light
Flashing light
Red LED:
Steady light
Flashing
Operation
The operation of Disturbance report function DRPRDRE has to be set
Disabled is selected, note that no disturbance report is registered, and none sub-function will
operate (the only general parameter that influences Sequential of events (SOE)).
Application manual
shows the relations between Disturbance report, included functions and function
In Service
Internal failure
No power supply
A Disturbance Report is triggered
The IED is in test mode
Triggered on binary signal N with
The IED is in configuration mode
SetLEDN = Enabled
Enabled or Disabled . If
Section 14
Monitoring
IP14874-1 v1
M12179-64 v6
M12179-82 v5
363