ABB RELION 670 Series Applications Manual page 180

Busbar protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 7
Current protection
ANSI10000031 V1 EN-US
Figure 89: Relay characteristic angle given in degree
In a transmission network a normal value of RCA is about 80°.
VPolMin : Minimum polarization (reference) voltage % of VBase .
I>Dir : Operate residual current level for directional comparison scheme. The setting is given in %
IBase . The pickup forward or pickup reverse signals can be used in a communication scheme.
of
The appropriate signal must be configured to the communication scheme block.
7.5
Thermal overload protection, two time constants
TRPTTR (49)
7.5.1
Identification
Function description
Thermal overload protection, two
time constants
174
Reverse
Area
AngleRCA
Iop = I2
Forward
Area
ANSI10000031-1-en.vsd
IEC 61850
IEC 60617
identification
identification
TRPTTR
SYMBOL-A V1 EN-US
1MRK 505 337-UUS A
Vpol=-V2
ANSI/IEEE C37.2
device number
49
Application manual
IP14513-1 v4
M14877-1 v2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reb670

Table of Contents