ABB RELION 670 Series Applications Manual page 141

Busbar protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 505 337-UUS A
Main CTs
ANSI06000127 V2 EN-US
Figure 73: Principle CT connections for the complete station
This summation type bus differential protection still has the same main CT requirements as
outlined in section
main CT ratio differences can be tolerated up to 10:1 (for example, 3000/5A CT can be
balanced against CT"s as low as 300/5)
different main CT ratios are compensated numerically by a parameter setting
main CT shall not saturate quicker than 2 ms ( refer to section
e.m.f. requirements"
However, due to the summation principle this type of busbar protection scheme has the following
limitations:
Application manual
LA
LB
IA1
IB1
52
52
A
B
C
N
A
IA2
IB2
CT1
"Rated equivalent secondary e.m.f.
for detailed CT requirements regarding main CT knee-point voltage)
LX
IX1
52
B
C
N
A
B
IX2
CT2
. . .
CT24
IED
with 1A
CT inputs
requirements". Some of these are:
Differential protection
A-bus
C
N
Summation CTs
ANSI06000127_2_en.vsd
"Rated equivalent secondary
Section 6
135