1MRK 505 337-UUS A
Control operation can be performed from the local IED HMI. If the administrator has defined users
with the IED Users tool in PCM600, then the local/remote switch is under authority control. If not,
the default (factory) user is the SuperUser that can perform control operations from the local IED
HMI without LogOn. The default position of the local/remote switch is on remote.
QCBAY
ANSI05000116 V1 EN-US
Figure 122: Signal flow between apparatus control function blocks
Accepted originator categories for PSTO
If the requested command is accepted by the authority, the value will change. Otherwise the
attribute
during a command, then the command is aborted.
The accepted originator categories for each PSTO value are shown in
Table 39: Accepted originator categories for each PSTO
Permitted Source To Operate
0 = Off
1 = Local
2 = Remote
3 = Faulty
4 = Not in use
Table continues on next page
Application manual
SCSWI
SCILO
SCSWI
SCILO
blocked-by-switching-hierarchy is set in the cause signal. If the PSTO value is changed
IEC 61850
SXCBR
SXCBR
SXCBR
SXSWI
Originator (orCat)
4,5,6
1,4,5,6
2,3,4,5,6
4,5,6
4,5,6
189
152
989
en05000116_ansi.vsd
Table 39
Section 12
Control
281