ABB RELION 670 Series Applications Manual page 343

Busbar protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 505 337-UUS A
Name of input
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16
The sum of the numbers in column "Value when activated" when all INx (where 1≤x≤16) are active
that is=1; is 65535. 65535 is the highest boolean value that can be converted to an integer by the
B16I function block.
13.8
Boolean to integer conversion with logical node
representation, 16 bit BTIGAPC
13.8.1
Identification
Function description
Boolean to integer conversion with
logical node representation, 16 bit
13.8.2
Application
Boolean 16 to integer conversion with logic node representation function BTIGAPC is used to
transform a set of 16 binary (logical) signals into an integer. BTIGAPC can receive an integer from a
station computer – for example, over IEC 61850–8–1. These functions are very useful when you
want to generate logical commands (for selector switches or voltage controllers) by inputting an
integer number. BTIGAPC has a logical node mapping in IEC 61850.
Application manual
Type
Default
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
IEC 61850
identification
BTIGAPC
Description
Value when
activated
Input 1
1
Input 2
2
Input 3
4
Input 4
8
Input 5
16
Input 6
32
Input 7
64
Input 8
128
Input 9
256
Input 10
512
Input 11
1024
Input 12
2048
Input 13
4096
Input 14
8192
Input 15
16384
Input 16
32768
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Section 13
Logic
Value when
deactivated
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
SEMOD175753-1 v4
SEMOD175757-2 v5
SEMOD175849-4 v5
337