ABB RELION 670 Series Applications Manual page 158

Busbar protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 7
Current protection
values are updated not more often than once every five years. In many cases this time interval is
still longer. Investigate the maximum load current that different equipment on the line can
withstand. Study components such as line conductors, current transformers, circuit breakers, and
disconnectors. The manufacturer of the equipment normally gives the maximum thermal load
current of the equipment.
The maximum load current on the line has to be estimated. There is also a demand that all faults,
within the zone that the protection shall cover, must be detected by the phase overcurrent
protection. The minimum fault current Iscmin, to be detected by the protection, must be
calculated. Taking this value as a base, the highest pick up current setting can be written
according to equation 29.
£
Ipu
0.7 Isc min
EQUATION1263 V2 EN-US
where:
0.7
Iscmin is the smallest fault current to be detected by the overcurrent protection.
As a summary the pickup current shall be chosen within the interval stated in equation 30.
Im ax
×
1.2
k
EQUATION1264 V2 EN-US
The high current function of the overcurrent protection, which only has a short delay of the
operation, must be given a current setting so that the protection is selective to other protection in
the power system. It is desirable to have a rapid tripping of faults within as large portion as
possible of the part of the power system to be protected by the protection (primary protected
zone). A fault current calculation gives the largest current of faults, Iscmax, at the most remote
part of the primary protected zone. Considerations have to be made to the risk of transient
overreach, due to a possible DC component of the short circuit current. The lowest current setting
of the most rapid stage, of the phase overcurrent protection, can be written according to
³
I
1.2
high
EQUATION1265 V1 EN-US
where:
1.2
k
t
Iscmax is the largest fault current at a fault at the most remote point of the primary protection zone.
The operate times of the phase overcurrent protection has to be chosen so that the fault time is
so short that protected equipment will not be destroyed due to thermal overload, at the same
time as selectivity is assured. For overcurrent protection, in a radial fed network, the time setting
152
×
is a safety factor
£
£
×
Ipu 0.7 Isc min
× ×
k I
t
sc
max
is a safety factor
is a factor that takes care of the transient overreach due to the DC component of the fault current and can
be considered to be less than 1.05
1MRK 505 337-UUS A
(Equation 29)
(Equation 30)
(Equation 31)
Application manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reb670

Table of Contents