1MRK 505 337-UUS A
number of elements per phase in series and parallel. Normally values required are given by
capacitor bank supplier.
For fuse supervision normally only this alarm level is used and a suitable voltage level is 3-5% if the
ratio correction factor has been properly evaluated during commissioning.
For other applications it has to be decided case by case.
tAlarm : The time delay for alarm is set by this parameter. Normally, few seconds delay can be used
on capacitor banks alarm. For fuse failure supervision (SDDRFUF) the alarm delay can be set to
zero.
8.5
Loss of voltage check LOVPTUV (27)
8.5.1
Identification
Function description
Loss of voltage check
8.5.2
Application
The trip of the circuit breaker at a prolonged loss of voltage at all the three phases is normally
used in automatic restoration systems to facilitate the system restoration after a major blackout.
Loss of voltage check (LOVPTUV, 27) generates a TRIP signal only if the voltage in all the three
phases is low for more than the set time. If the trip to the circuit breaker is not required, LOVPTUV
(27) is used for signallization only through an output contact or through the event recording
function.
8.5.3
Setting guidelines
Loss of voltage check (LOVPTUV, 27) is in principle independent of the protection functions. It
requires to be set to open the circuit breaker in order to allow a simple system restoration
following a main voltage loss of a big part of the network and only when the voltage is lost with
breakers still closed.
All settings are in primary values or per unit. Set operate level per phase to typically 70% of the
global parameter
8.5.3.1
Advanced users settings
For advanced users the following parameters need also to be set. Set the length of the trip pulse
to typical
27), if some but not all voltage are low, to typical 5.0 seconds and set the time delay for enabling
the function after restoration
Application manual
VBase level. Set the time delay tTrip =5-20 seconds.
tPulse =0.15 sec. Set the blocking time tBlock to block Loss of voltage check (LOVPTUV,
tRestore to 3 - 40 seconds.
IEC 61850
IEC 60617
identification
identification
LOVPTUV
-
Voltage protection
ANSI/IEEE C37.2
device number
27
Section 8
SEMOD171868-1 v2
SEMOD171954-2 v2
SEMOD171876-4 v3
SEMOD171929-4 v5
SEMOD171929-8 v4