Section 12
Control
IED
Apparatus
Control
CLOSE/OPEN
ANSI08000227 V1 EN-US
Figure 121: Overview of the apparatus control functions
Features in the apparatus control function:
•
Operation of primary apparatuses
•
Select-Execute principle to give high security
•
Selection and reservation function to prevent simultaneous operation
•
Selection and supervision of operator place
•
Command supervision
•
Block/deblock of operation
•
Block/deblock of updating of position indications
•
Substitution of position indications
•
Overriding of interlocking functions
•
Overriding of synchronism check
•
Pole discrepancy supervision
•
Operation counter
•
Suppression of mid position
The apparatus control function is realized by means of a number of function blocks designated:
•
Switch controller SCSWI
•
Circuit breaker SXCBR
•
Circuit switch SXSWI
•
Bay control QCBAY
•
Position evaluation POS_EVAL
•
Bay reserve QCRSV
•
Reservation input RESIN
•
Local remote LOCREM
•
Local remote control LOCREMCTRL
The signal flow between the function blocks is shown in Figure 122. To realize the reservation
function, the function blocks Reservation input (RESIN) and Bay reserve (QCRSV) also are included
in the apparatus control function. The application description for all these functions can be found
below. The function SCILO in the Figure below is the logical node for interlocking.
280
Station HMI
Local
Local
HMI
HMI
IED
Apparatus
Control
CLOSE/OPEN
breakers disconnectors grounding switches
cc
GW
Station bus
Local
HMI
IED
Apparatus
Control
CLOSE/OPEN
ANSI08000227.vsd
1MRK 505 337-UUS A
Application manual