Busbar protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 7
Current protection
7.8.3
Setting guidelines
GlobalBaseSel : Selects the global base value group used by the function to define ( IBase ), ( VBase )
SBase ).
and (
Operation : With the parameter Operation the function can be set Enabled / Disabled .
Mode : The voltage and current used for the power measurement. The setting possibilities are
shown in table 33.
Table 33:
Set value
A, B, C
Arone
PosSeq
AB
BC
CA
A
B
C
The function has two stages that can be set independently.
With the parameter
186
Complex power calculation
Mode
OpMode1(2) the function can be set Enabled / Disabled .
Formula used for complex power calculation
*
*
=
×
+
×
+
S
V
I
V
I
A
A
B
B
EQUATION2055-ANSI V1 EN-US
*
=
×
-
×
S
V
I
V
I
AB
A
BC
EQUATION2056-ANSI V1 EN-US
*
= ×
×
S
3
V
I
PosSeq
PosSeq
EQUATION2057-ANSI V1 EN-US
*
*
=
×
-
S
V
(
I
I
)
AB
A
B
EQUATION2058-ANSI V1 EN-US
*
*
=
×
-
S
V
(
I
I
)
BC
B
C
EQUATION2059-ANSI V1 EN-US
*
*
=
×
-
S
V
(
I
I
)
CA
C
A
EQUATION2060-ANSI V1 EN-US
*
= ×
×
S
3
V
I
A
A
EQUATION2061-ANSI V1 EN-US
*
= ×
×
S
3
V
I
B
B
EQUATION2062-ANSI V1 EN-US
*
= ×
×
S
3
V
I
C
C
EQUATION2063-ANSI V1 EN-US
1MRK 505 337-UUS A
*
×
V
I
C
C
(Equation 45)
*
C
(Equation 46)
(Equation 47)
(Equation 48)
(Equation 49)
(Equation 50)
(Equation 51)
(Equation 52)
(Equation 53)
Application manual
SEMOD172134-4 v7