ABB RELION 670 Series Applications Manual page 333

Busbar protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 505 337-UUS A
12.8.3
Setting guidelines
The parameters for the single point generic control 8 signals (SPC8GAPC) function are set via the
local HMI or PCM600.
Operation : turning the function operation Enabled / Disabled .
There are two settings for every command output (totally 8):
Latchedx : decides if the command signal for output x is Latched (steady) or Pulsed .
tPulsex : if Latchedx is set to Pulsed , then tPulsex will set the length of the pulse (in seconds).
12.9
AutomationBits, command function for DNP3.0
AUTOBITS
12.9.1
Identification
Function description
AutomationBits, command function
12.9.2
Application
Automation bits, command function for DNP3 (AUTOBITS) is used within PCM600 in order to get
into the configuration the commands coming through the DNP3.0 protocol.The AUTOBITS
function plays the same role as functions GOOSEBINRCV (for IEC 61850) and MULTICMDRCV (for
LON).AUTOBITS function block have 32 individual outputs which each can be mapped as a Binary
Output point in DNP3. The output is operated by a "Object 12" in DNP3. This object contains
parameters for control-code, count, on-time and off-time. To operate an AUTOBITS output point,
send a control-code of latch-On, latch-Off, pulse-On, pulse-Off, Trip or Close. The remaining
parameters are regarded as appropriate. For example, pulse-On, on-time=100, off-time=300,
count=5 would give 5 positive 100 ms pulses, 300 ms apart.
For description of the DNP3 protocol implementation, refer to the Communication manual.
12.9.3
Setting guidelines
AUTOBITS function block has one setting, (
function. These names will be seen in the DNP3 communication management tool in PCM600.
Application manual
PSTO is the universal operator place selector for all control functions. Even if PSTO
can be configured to allow LOCAL or ALL operator positions, the only functional
position usable with the SPC8GAPC function block is REMOTE.
IEC 61850
identification
for DNP3
IEC 60617
identification
AUTOBITS
-
Operation : Enabled / Disabled ) enabling or disabling the
GUID-C3BB63F5-F0E7-4B00-AF0F-917ECF87B016 v4
ANSI/IEEE C37.2
device number
-
Section 12
Control
SEMOD176518-4 v5
SEMOD158589-1 v3
SEMOD158637-5 v4
SEMOD158639-5 v3
327