ABB RELION 670 Series Applications Manual page 246

Busbar protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 11
Secondary system supervision
ANSI12000143 V1 EN-US
Figure 104: Application of VDSPVC
11.2.3
Setting guidelines
The parameters for Fuse failure supervision VDSPVC are set via the local HMI or PCM600.
The voltage input type (phase-to-phase or phase-to-neutral) is selected using
ConTypePilot parameters, for main and pilot fuse groups respectively.
The settings
VBase . Set VBase to the primary rated phase-to-phase voltage of the potential voltage
transformer.
group, that is used by VDSPVC (60), is set by the setting parameter
240
The connection type for the main and the pilot fuse groups must be consistent.
Vdif Main block , Vdif Pilot alarm and VSealIn are in percentage of the base voltage,
VBase is available in the Global Base Value groups; the particular Global Base Value
A
B
C
Main Vt circuit
IED
FuseFailSupvn
ANSI12000143-1-en.vsd
1MRK 505 337-UUS A
GUID-0D5A517C-1F92-46B9-AC2D-F41ED4E7C39E v1
GUID-52BF4E8E-0B0C-4F75-99C4-0BCB22CDD166 v2
GUID-0B298162-C939-47E4-A89B-7E6BD7BEBB2C v2
ConTypeMain and
GlobalBaseSel .
Application manual