ABB RELION 670 Series Applications Manual page 197

Busbar protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 505 337-UUS A
Operate
Line
Margin
Operating point
without
turbine torque
IEC06000315 V2 EN-US
Figure 95: Reverse power protection with underpower IED and overpower IED
7.9.3
Setting guidelines
GlobalBaseSel : Selects the global base value group used by the function to define ( IBase ), ( VBase )
and (
SBase ).
Operation : With the parameter Operation the function can be set Enabled / Disabled .
Mode : The voltage and current used for the power measurement. The setting possibilities are
shown in table 34.
Table 34: Complex power calculation
Set value
A,B,C
Arone
PosSeq
A,B
B,C
C,A
Table continues on next page
Application manual
Underpower IED
Q
Operate
Line
Margin
P
Operating point
without
turbine torque
Mode
Overpower IED
Q
P
IEC06000315-2-en.vsd
Formula used for complex power calculation
*
=
×
+
S
V
I
V
A
A
EQUATION2038 V1 EN-US
*
-
=
×
S
V
I
AB
A
EQUATION2039 V1 EN-US
= ×
×
S
3 V
I
PosSeq
PosSeq
EQUATION2040 V1 EN-US
*
-
=
×
S
V
(I
AB
A
EQUATION2041 V1 EN-US
*
-
=
×
S
V
(I
BC
B
EQUATION2042 V1 EN-US
*
-
=
×
S
V
(I
CA
C
EQUATION2043 V1 EN-US
*
*
×
+
×
I
V
I
B
B
C
C
*
×
V
I
BC
C
*
*
)
I
B
*
)
I
C
*
)
I
A
Section 7
Current protection
SEMOD172150-4 v7
(Equation 58)
(Equation 59)
(Equation 60)
(Equation 61)
(Equation 62)
(Equation 63)
191