Setting Bcb Parameters; Setting The T/H Sensor - Huawei UPS5000-E-200K-SM User Manual

50 kva power modules
Hide thumbs Also See for UPS5000-E-200K-SM:
Table of Contents

Advertisement

UPS5000-E-(200 kVA-300 kVA)
User Manual (50 kVA Power Modules)
1.
2.
Step 4 Connect the device on the NetEco app.
----End

4.1.3.2 Setting BCB Parameters

Prerequisites
A BCB box is installed.
Procedure
Step 1 Choose System Info > Settings > Dry Contact Set, set MUE05A connection to
Enable, and set BCB connection [OL] and Battery breaker [STA] to Enable.
Figure 4-4 BCB connection settings
----End

4.1.3.3 Setting the T/H Sensor

Context
The ambient T/H sensor has been installed by referring to the installation section.
The ambient T/H sensor can also be used as a battery temperature sensor. The
monitoring module distinguishes these two types of sensors through their DIP
switch settings.
Issue 17 (2023-07-10)
Choose System Settings > NMS Application > BIN > Communication
Parameters on the WebUI. Set parameters as follows:
Address type: Domain name
Server domain name and Port number: Retain the default values.
Connection test link setup port: FE
Click Test Connect. After the test is successful, click Submit.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Single UPS Commissioning
175