UPS5000-E-(200 kVA-300 kVA) User Manual (50 kVA Power Modules) Issue Date 2023-07-10 HUAWEI DIGITAL POWER TECHNOLOGIES CO., LTD.
Page 2
Notice The purchased products, services and features are stipulated by the contract made between Huawei Digital Power Technologies Co., Ltd. and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
250 kVA, and 300 kVA. NO TE ● The UPS5000-E-200K-SM supports cable routing from the top or bottom. ● The UPS5000-E-200K-FM supports cable routing from the top and can support cable routing from the bottom if a cable entry cabinet is installed for the non-isolation protection model.
Page 68
● The IP21 component cannot be configured for the UPS5000-E-300K-SMT and UPS5000- E-200K-FM. If cables are routed in and out from the top for the UPS5000-E-200K-SM, the IP21 component cannot be configured. Issue 17 (2023-07-10)
Page 79
DC power cable should not be longer than 50 meters. Table 3-2 Table 3-3 list the requirements for power cable terminals of the UPS5000-E-200K-SM/FM. Table 3-2 Power cable terminal requirements for the UPS5000-E-200K-SM Port Connection Bolt Bolt Hole...
UPSs and then use screws to tighten the connecting kits to the cabinet according to the following figures: ● Figure 3-113 shows the connection point for the UPS5000-E-200K-SM and UPS5000-E-300K-SM/SMT. ● Figure 3-114 shows the connection point for the UPS5000-E-200K-FM.
----End 3.3.2 Connecting Power Cables Context Cable connection for the UPS5000-E-200K-SM is used as an example. The parallel power cables for different UPS models can be connected in a similar way. Procedure Step 1 Ground each UPS in a parallel system separately, and connect power cables and battery cables according to 3.2 Installing a Single...