Step 5 If the system has connected to the remote EPO switch, you need to choose
Monitoring > UPS System > Running Parameter > System Settings on the
WebUI and set EPO detection to Enable.
Step 6 View the system running status diagram on the LCD to check that the UPS is
working in bypass mode.
----End

4.1.3 Setting Parameters for Optional Components

4.1.3.1 (Optional) iManager-M Service Access

● If the 4G module has been installed, use the method described in the 4G
● If the device has been connected to the LAN switch or router, use the method
4G Module Access Scenario (LCD)
Step 1 Set iManager-M Service parameters.
On the LCD, choose System Status > Settings > Settings Wizard. On the
iManager-M Service screen, set Enable/Disable to Enable and Access channel to
4G.
Issue 17 (2023-07-10)
NO TE
● After you set parameters on the Settings Wizard screen, choose System Info > Settings
> System Settings. Check that Requisite modules and Redundant modules match the
actual values.
● If dry contact signals are connected to the system, choose System Info > Settings > Dry
Contact Set. Check that the connected dry contacts have been enabled and that the
disconnected dry contacts have been disabled.
NO TICE
module access scenario (LCD or WebUI) to complete iManager-M service
access.
described in the FE access scenario (LCD or WebUI) to complete iManager-M
service access.
NO TE
If Access authentication code on the iManager-M Service screen is empty, obtain the
authentication code from the position shown in the following figure and enter it in Access
authentication code.