Figure 3-11 Tightening expansion bolts
----End
Unsecured Installation
Step 1 Adjust the four anchor bolts at the bottom of the UPS cabinet until all the four
castors at the bottom hang in the air and the anchor bolts bear all of the cabinet
weight, as shown in
Figure 3-12 Castors adjustment
Step 2 Check the cabinet levelness using a level. If the cabinet is not level, wrench the
anchor bolts.
----End
Issue 17 (2023-07-10)
Figure
Copyright © Huawei Digital Power Technologies Co., Ltd.
3-12.
3 Installation