UPS5000-E-(350 kVA–800 kVA)
User Manual (50 kVA Power Modules)
Figure 4-3 Starting the inverter
----End

4.1.4 Powering On Loads

Context
After the inverter starts, the UPS transfers to inverter mode, and the Bypass mode
alarm on the LCD disappears.
Procedure
Step 1 After confirming that the battery string is properly connected, switch on the
battery string input circuit breaker. If there are multiple battery strings, switch on
the circuit breaker for each battery string and then the general circuit breaker
between the battery strings and the UPS. The No battery alarm on the LCD
disappears.
Step 2 Turn on the downstream output switch of the UPS to supply power to loads.
----End

4.1.5 (Optional) Setting Parameters for the BCB Box

Prerequisites
A BCB box is installed.
Procedure
Step 1 On the System Info > Settings > Dry Contact Set screen, set MUE05A
connection to Enable, and set BCB connection [OL] and Battery breaker [STA]
to Enable.
Issue 15 (2022-01-30)
NO TE
If the power module receives a startup command when it cannot be started, the startup
command will be kept for 1 minute. Within 1 minute, if there is no situation (for example,
the power module encounters other faults, executes a shutdown command, or a fault is
rectified) that requires the startup command to be cleared and the power module becomes
able to start, then the power module responds to the startup command.
Copyright © Huawei Technologies Co., Ltd.
4 Operations
146