If the configurable digital I/O is used as a general digital I/O, various low current operations such as
solenoid valves for voltage and signal exchanges with PLC systems or peripherals can be performed.
The following is how to use the configurable digital I/O:
If dry contact input is received
This is a method of connecting a switch or contact between the VIO terminal of terminal blocks
TBCI1-TBCI4 and Ixx terminals. The output of the external device only acts on the open/close of the
contact through the relay, so it is electrically insulated from external devices.
K1
NPN output
PNP output
(Sink type)
(Source type)
with Relay
with Relay
If wet contact input is received
It receives voltage type signals from external devices. If the output of the target device is source
type, it receives a voltage of 24V/0V as input. If the output of the target device is sink type, a relay
can be added to receive voltage of 24V/0V as input. Because voltage input requires a reference, the
external devices and the external power supply must be connected to a common ground.
K1
PNP output
(Source type)
NPN output
(Sink type)
with Relay
Doosan Robotics Installation(A-Series) Manual v1.8
Dry Contact Connection
K1
K2
K2
Wet Contact Connection
24V
(Voltage/Current from Ext. Source)
K1
SW
Pushbutton
/ Switch
Common Ground
Safety Controller
VIO (24V)
VIO
TBCI1~TBCI4
SW
I01~I16
GIO
Safety Controller
VIO (24V)
VIO
TBCI1~TBCI4
I01~I16
GIO
70
Board
Board