Fig. 8 Switch-Off Ramp - T - Beckhoff KS2535, KL2545 Manual

Pulse width current terminals
Table of Contents

Advertisement

Fig. 8: Switch-off ramp - t
Valve curve
Feature bit R32.4 [} 45] must be set in order to activate the valve curve.
The following parameters can be set:
Name
Overlap threshold value - x
Overlap output value - y
Bend compensation -threshold
value- x
2
Bend compensation - output value -
y
2
Area compensation - threshold
value - x
3
The characteristic curve is divided into four regions:
I
Overlapping
II
Bend compensation
III, III'
Area compensation
IV
End region
KL2535/KS2535, KL2545/KS2545
Regis-
Value range
ter
0 to 1000
R40
1
[} 46]
0 to 1000
R41
1
[} 46]
0 to 1000
R42
[} 46]
0 to 1000
R43
[} 46]
0 to 1000
R44
[} 46]
Version: 2.1.0
Description
The overlap range ends at this process data
value; the resolution is 0.1% (as a fraction of
32767)
The maximum output current in the overlap
region; the resolution is 0.1% (with reference
to the output current that has been set in
register R36 [} 45])
The bend compensation range ends at this
process data value; the resolution is 0.1% (as
a fraction of 32767)
The maximum output current in the bend
compensation region; the resolution is 0.1%
(with reference to the output current that has
been set in register R36 [} 45])
The area compensation region ends at this
process data value; the resolution is 0.1% (as
a fraction of 32767)