Fig. 23 Elx1054 - Dip Switch - Beckhoff ELX1052 Operating Manual

Two, four and eight channel digital input terminals for namur sensors, ex i
Hide thumbs Also See for ELX1052:
Table of Contents

Advertisement

Mounting and wiring
DIP switch
The DIP switch allows to invert the input signal for each channel of the ELX1054 separately. For the
inversion of the signal, the DIP switch must be set to the ON position.
Fig. 23: ELX1054 - DIP switch
Switch position
ON
OFF
LED display
The following tables are assigned to the respective LED number of a channel.
LED display if DIP switch of the associated channel is in position OFF (default):
Input LED
Error LED
off
on
off
off
on
on
on
off
LED display if DIP switch of the associated channel is in position ON:
Input LED
Error LED
off
on
off
off
on
on
on
off
30
for sensor
negative switching
positive switching (default)
Meaning
Error detection: open- circuit on channel (I < 200 µA typ.)
Usual operation: NAMUR sensor on channel in non-conductive state
("0"; according to IEC 60947-5-6)
Error detection: short-circuit on channel (I > 6.3 mA typ.)
Usual operation: NAMUR sensor on channel in conducting state
("1"; according to IEC 60947-5-6)
Meaning
Error detection: short-circuit on channel (I > 6.3 mA typ.)
Usual operation: NAMUR sensor on channel in conducting state
("1"; according to IEC 60947-5-6)
Error detection: open- circuit on channel (I < 200 µA typ.)
Usual operation: NAMUR sensor on channel in non-conductive state
("0"; according to IEC 60947-5-6)
Version: 2.0.0
ELX1052, ELX1054 and ELX1058