Kl2545 - Contact Assignment; Fig. 21 Kl2545 - Contact Assignment - Beckhoff KS2535, KL2545 Manual

Pulse width current terminals
Table of Contents

Advertisement

Mounting and wiring
3.6

KL2545 - Contact assignment

Risk of injury through electric shock and damage to the device!
Bring the Bus Terminals system into a safe, de-energized state before starting mounting, disassembly or
wiring of the Bus Terminals.
Fig. 21: KL2545 - Contact assignment
Left-hand section of the housing
Terminal point
No.
Encoder A, A
1
Encoder B, A
2
Encoder Power +24 V 3
Input 1
4
Encoder A, B
5
Encoder B, B
6
Encoder Power 0 V
7
Input 2
8
28
WARNING
Connection for
Encoder A, connection A
Encoder B, connection A
Encoder supply (from positive power contact)
Digital input 1 (24 V
).
DC
The current counter value is saved as a reference mark in the latch register if
bit CW.1 is set in the control word and a rising edge occurs at digital input 1.
Encoder A, connection B
Encoder B, connection B
Encoder supply (from negative power contact)
Digital input 2 (24 V
).
DC
The current counter value is saved as a reference mark in the latch register if
bit CW.2 is set in the control word and a rising edge occurs at digital input 2.