Beckhoff KS2535, KL2545 Manual page 26

Pulse width current terminals
Table of Contents

Advertisement

Mounting and wiring
High Density Terminals ELx8xx, KLx8xx (HD)
The conductors of the HD Terminals are connected without tools for single-wire conductors using the direct
plug-in technique, i.e. after stripping the wire is simply plugged into the terminal point. The cables are
released, as usual, using the contact release with the aid of a screwdriver. See the following table for the
suitable wire size width.
Terminal housing
Wire size width (single core wires)
Wire size width (fine-wire conductors)
Wire size width (conductors with a wire end sleeve)
Wire size width (ultrasonically "bonded" conductors)
Wire stripping length
Shielding
Shielding
Analog sensors and actors should always be connected with shielded, twisted paired wires.
26
Version: 2.1.0
High Density Housing
2
0.08 ... 1.5 mm
2
0.25 ... 1.5 mm
2
0.14 ... 0.75 mm
2
only 1.5 mm
(see notice [} 25]!)
8 ... 9 mm
KL2535/KS2535, KL2545/KS2545