Beckhoff KS2535, KL2545 Manual page 45

Pulse width current terminals
Table of Contents

Advertisement

R31: Code word register
If you write values into the user registers without first entering the user code word (0x1235) into the code
word register, the terminal will not accept the supplied data. The code word is reset if the terminal is
restarted.
R32: Feature register
The feature register specifies the terminal's configuration.
Bit
R32.15
R32.14
Name
disMixedDecay
-
Bit
R32.7 R32.6
R32.5
Name
-
enRamps enDithering
Legend
Bit
Name
R32.15
disMixedDecay
R32.14-R32.9 -
R32.8
enUserStartValue 1
R32.7
-
R32.6
enRamps
R32.5
enDithering
R32.4
enValveCurve
R32.3
enAverageNotati
on
R32.2
disWatchdog
R32.1
enManuScale
R32.0
enUserScale
R33: User scaling - offset
If user-scaling is active (R32.0 [} 45]=1) this register specifies the offset for the user-scaling.
R34: User scaling - gain
If user-scaling is active (R32.0 [} 45]=1) this register specifies the gain for the user-scaling.
R35: User's switch-on value
If the user switch-on value is active (R32.8 [} 45]=1) and if the activated watchdog (R32.2 [} 45]=0
triggers following a fieldbus or terminal bus error continuing for 100 ms, the output will be set to this value.
R36: Maximum output current
This register specifies the maximum output current. The unit is 1 mA (for example: 1000
KL2535: maximum 1000 mA (default: 1000
KL2545: maximum 3500 mA (default: 3500
KL2535/KS2535, KL2545/KS2545
R32.13
R32.12
R32.11
-
-
-
R32.4
R32.3
enValveCurve
enAverageNotation
Description
1
Mixed Decay is deactivated
bin
reserved
User switch-on value active (see R35 [} 45])
bin
reserved
1
Process data ramps [} 18] are active (see R45
bin
[} 46] + R46 [} 47])
1
Dithering [} 16] is active (see R37 [} 46], R38
bin
[} 46] + R39 [} 46]); bit CB1.0 [} 40] = 1 must be
set in addition
1
Valve curve [} 17] is active (see R40 [} 46], R41
bin
[} 46], R42 [} 46], R43 [} 46] + R44 [} 46])
0
Two's complement representation is active
bin
1
Signed amount representation active
bin
1
Internal 100 ms watchdog deactivated
bin
1
Manufacturer scaling is active
bin
1
User scaling active (see R33 [} 45]+ R34 [} 45])
bin
)
dec
)
dec
Version: 2.1.0
Access from the user program
R32.10
R32.9
-
-
R32.2
R32.1
disWatchdog
enManuScale
= 1 A).
dec
R32.8
enUserStartValue
R32.0
enUserScale
default
0
bin
0
bin
0
bin
0
bin
0
bin
0
bin
0
bin
0
bin
0
bin
)
bin
45